Step 5. Field Wiring – Refer to Section A for millivolt appliances and Section B for electronic appliances.
A. Millivolt Wiring – Units may be fitted at the factory with either a Honeywell millivolt gas control valve or an SIT millivolt gas control valve. Both valves have been tested with and approved for use with these appliances and are listed accordingly. Refer to Figure 12 for wiring of Honeywell systems and Figure 13 for wiring of SIT systems.
The gas valve has been set in place and has been
CAUTION: DO NOT CONNECT THE WALL SWITCH TO A 120V POWER SUPPLY.
Honeywell Millivolt Wiring Diagram
If any of the original wire as supplied must be replaced, it must be replaced with Type AWM 105° C – 18 GA. wire.
WHT BK
TH | * |
BK
TP | TH | TPTH |
|
Limit
Switch
T P | TH | |
TP | ||
|
ThermopileBK
* For Wall Switch Attachment Only.
Figure 12
SIT Millivolt Wiring Diagram
If any of the original wire as supplied must be replaced, it must be replaced with Type AWM 105° C – 18 GA. wire.
Limit Switch
|
| BK |
BK |
| TH TP |
|
| TP |
|
| TH |
| Thermopile | |
BK |
|
|
| * | WHT |
|
|
* For Wall Switch Attachment Only.
Figure 13
Note: Optional wall switch not supplied. If the optional wall switch is not installed, the ends of the 15' (4.5m) coiled wire must be connected with a wire nut (not supplied) for the appliance to operate.
B. Electronic Wiring – The electronic appliance must be connected to the main power supply. To install:
1.Route a
Figures 14 and 16 ).
2.Locate and install a low voltage (24V) wall switch (not supplied) in the desired location. Connect the low voltage wire to this switch (see Figure 14 ).
3.After wiring is complete, replace the appli- ance junction box cover and secure with the hex head screws previously removed.
IMPORTANT:Groundleadmustbeconnected to the green screw located on the outlet box. See Figure 14 . Failure to do so will result in apotentialsafetyhazard.Theappliancemust be electrically grounded in accordance with local codes or, in the absence of local codes, the National Electrical Code, ANSI/NFPA 70- (latest edition). (In Canada, the current CSA
Electronic Wiring Diagram (Honeywell)
(Optional ON/OFF Switch Wiring)
1.If any of the original wire as supplied must be replaced,
1.it must be replaced with Type AWM 105° C – 18 GA. wire.
2.120V, 60Hz – Less than 3 amps.
| Gas Valve |
|
| OPT. ACCESSORY |
|
| CONTROL |
| PILOT | SWITCH |
|
| IGNITER |
| ASSEMBLY | W | VAC. |
BK |
|
|
| BK | 120 |
|
|
|
|
| |
| R |
|
| G |
|
|
|
|
|
| |
| BL |
|
|
|
|
|
|
| G |
|
|
|
|
|
| Break |
|
|
|
|
| Off Tab |
|
|
|
|
| To Opposite Side |
|
|
|
| Junction Box |
| |
|
|
| W | Transf. |
|
|
|
| B |
| |
|
|
| G | 120 V. |
|
|
|
| BL | 24 V |
|
|
|
|
|
| |
|
|
| R |
|
|
BK |
|
|
|
| BK |
|
|
|
|
| |
| WHT | BK | BK |
|
|
| OPTIONAL |
|
| LIMIT |
|
| ON/OFF SWITCH |
| SWITCH |
| |
| OR |
|
|
|
|
| WALL SWITCH |
|
|
| |
| Factory Wired | Field Wired |
Figure 14
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Step 6. Connecting Gas Line – Make gas line connections. All codes require a
The gas control valve is located in the lower control compartment. To access the valve remove the removable access panel and set aside
(Figure 15 ).
Note: To provide increased access to the lower control compartment, you may choose to remove the front log. To do so, undo the twists in the wires securing the log from below to each of the grate tines. After removal of the log cut the wires off closely to the log before reinstalling it. These are only required for shipping.
The millivolt control valve has a ³⁄₈" (10 mm) NPT thread inlet port. The electronic control valve has a ¹⁄₂" (13 mm) NPT thread inlet port and is fitted with a ¹⁄₂" x ³⁄₈" (13 mm x
10mm) NPT fitting. Both the millivolt and elec- tronic models are fitted with a gas flex line and shutoff valve, ³⁄₈" NPT. Plan the connections accordingly.
Gas Controls
on Valve
Removable
Access Panel
SIT Valve Shown
Figure 15
Secure all joints tightly using appropriate tools and sealing compounds (ensure propane resistant compounds are used in propane applica- tions). Turn on gas supply and test for gas leaks using a soapy water solution. Never use an
open flame to check for leaks.
A. Mix a 50% dish soap, 50% water solution.
B. Light the appliance (refer to the lighting instructions provided in the Homeowner's Care and Operation Instructions).
C. Brush all joints and connections with the soapy water solution to check for leaks. If bubbles are formed, or gas odor is detected, turn the gas control knob to the “OFF” position. Either tighten or refasten the leaking connection and retest as described above.
7