System Sensor 2W-B b Wiring Diagram, 4W-Band 4WT-B, Installation, Testing, Maintenance

Models: 2W-B

1 4
Download 4 pages 52.54 Kb
Page 3
Image 3
Figure 3b: Wiring Diagram, 4W-B and 4WT-B

Figure 3b: Wiring Diagram, 4W-B and 4WT-B

Figure 4: Recessed Test Switch Opening and SENS-RDR Position

AUX OR

+

 

EOL

SMOKE

 

RELAY

POWER

 

(A77-716B)

IDC

 

 

+

 

 

 

 

 

EOL

 

 

 

RESISTOR

4-WIRE

 

(5) (4) (3) (2) (1)

(5) (4) (3) (2) (1)

 

COM NO – IN/OUT + OUT + IN

COM NO – IN/OUT + OUT + IN

CONTROL

PANEL

 

 

 

 

 

4W-B or

4W-B or

POSITION SENS-RDR

AT AN ANGLE ON THE

OVAL AREA OR AT THE

CHAMBER OPENING

BY THE WORD “PAINT”

LED

RECESSED TEST SWITCH

Installation PUSH RECESSED SWITCH WITH A 0.18MAX.

DIAMETER TOOL

4WT-B

4WT-B

S0134-00

Installation

TestingLoop Verification (models 2W-B and 2WT-B only)WARNING

Remove power from alarm control unit or initiating device circuits before installing detectors.

NOTE: To install units so that corresponding LEDs are lined up, refer to the “Green LED” indicator on the base.

1.Wire the mounting base screw terminals per Figure 3a or Figure 3b, as applicable.

2.Place detector on the base and rotate clockwise. The detector will drop into the base and lock into place with a “click”.

3.After all detectors have been installed, apply power to the alarm control unit.

4.Test each detector as described in Testing.

5.Reset all the detectors at the alarm control unit.

6.Notify the proper authorities that the system is in operation.

Table 3: EZ Walk Test Detector ModesMaintenanceCAUTION

Dust covers are an effective way to limit the entry of dust into the smoke detector sensing chamber. However, they may not completely prevent airborne dust particles from entering the detector. Therefore, System Sensor recommends the removal of detectors before beginning construction or other dust producing activity. When returning the system to service, be sure to remove the dust covers from any detectors that were left in place during construction.

Testing

Detectors must be tested after installation and following maintenance.

NOTE: Before testing, notify the proper authorities that mainte- nance is being performed and the system will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent any unwanted alarms.

Ensure proper wiring and power is applied. After power up, allow 80 seconds for the detector to stabilize before testing.

Test i3 Series detectors as follows:

A. Test Switch

1.An opening for the recessed test switch is located on the detector housing (See Figure 4).

2.Insert a small screwdriver or allen wrench (0.18max.) into the test switch opening; push and hold.

3.If the detector is within the listed sensitivity limits, the detector’s red LED should light within five seconds.

S0135-00

B.Smoke Entry Test

Hold a smoldering punk stick or cotton wick at the side of the detector and gently blow the smoke through the detector until it alarms.

C.Direct Heat Method (models 2WT-B and 4WT-B only)

Using a 1000-1500 watt hair dryer, direct the heat toward either of the thermistors. Hold the heat source about 12 inches from the detector to avoid damage to the plastic.

NOTE: For the above tests, the detector will reset only after the power source has been momentarily interrupted.

If a detector fails any of the above test methods, its wiring should be checked and it should be cleaned as outlined in the Maintenance section. If the detector still fails, it should be replaced.

Notify the proper authorities when the system is back in service.

Loop Verification (models 2W-B and 2WT-B only)

Loop verification is provided by the EZ Walk loop test feature. This feature is for use with i3 Series compatible control panels or the i3 Series 2W-MOD module only. The EZ Walk loop test verifies the initiating loop wiring and provides visual status indication at each detector.

1.Ensure proper wiring and power is applied. Wait approxi- mately six minutes before performing EZ Walk test.

2.Place control panel or module in EZ Walk Test mode (refer to panel manufacturer’s manual or 2W-MOD manual D500- 46-00).

3.Observe the LEDs on each detector:

Table 3: EZ Walk Test Detector Modes

 

Green LED

Red LED

 

 

 

Proper Operation

Double blink 5 sec

 

 

 

Out of Sensitivity

Double Blink 5 sec

 

 

 

Freeze Condition

Double Blink 10 sec

 

 

 

NOTE: The EZ Walk loop test must not be used instead of alarm testing.

Maintenance

NOTE: Before performing maintenance on the detector, notify the proper authorities that maintenance is being performed and the system will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent any unwanted alarms.

Power must be removed from the detector before performing maintenance of any kind.

D100-96-00

3

I56-1800-07R

Page 3
Image 3
System Sensor b Wiring Diagram, 4W-Band 4WT-B, Installation, Testing, Loop Verification models 2W-Band 2WT-Bonly