System Sensor DH100LP specifications Electrical Ratings - includes base and detector

Models: DH100LP

1 8
Download 8 pages 20.5 Kb
Page 8
Image 8
Electrical Ratings — includes base and detector

[9] Model DH100LP Air Duct Smoke Detector Specifications

 

Operating Temperature:

+32° to +131° F

0° to +55° C

Storage Temperature:

–22° to +158° F

–30° to +70° C

Humidity:

10% to 93% R.H. noncondensing

 

Air Velocity:

100 to 4000 ft./min.

0.5 to 20.3 m/sec.

Dimensions:

14.38” L x 5.5” W x 2.75” D

36.5cm L x 14cm W x 7cm D

Weight:

3.25 pounds

1.5 kg

Electrical Ratings — includes base and detector

 

System Voltage:

12/24 VDC

 

Maximum Ripple Voltage:

4 Volts peak to peak

 

Start-up Capacitance:

0.02 µF maximum

 

Standby Ratings:

8.5 VDC minimum

 

 

35 VDC maximum

 

 

120 µA maximum

 

Alarm Ratings:

4.2 VDC minimum at 10mA

 

 

6.6 VDC maximum at 130mA

 

 

Alarm current must be limited to 130mA or less by the control panel.

 

If used, the RA400Z remote lamp operates within the specified alarm currents.

Reset Voltage:

2.50 VDC minimum

 

Reset Time:

0.3 Sec. maximum

 

Start-up Time:

34.0 Sec. maximum

 

 

 

 

Please refer to insert for the Limitations of Fire Alarm Systems

Three-Year Limited Warranty

System Sensor warrants its enclosed air duct smoke detector to be free from defects in materials and workmanship under normal use and ser- vice for a period of three years from date of manufacture. System Sensor makes no other express warranty for this air duct smoke detector. No agent, representative, dealer, or employee of the Company has the author- ity to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the air duct smoke detector which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Returns Department, RA #__________, 3825 Ohio

Avenue, St. Charles, IL 60174. Please include a note describing the mal- function and suspected cause of failure. The Company shall not be obli- gated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.

D200-15-00

8

I56-0083-07R

©2003 System Sensor

Page 8
Image 8