[8]Model DH400ACDCP Air Duct Smoke Detector Specifications
Description
HVAC air duct mounted ionization or photoelectronic smoke detector for separately powered systems or stand alone sys- tems. Auxiliary alarm relay contacts provide fan contactor shutdown to prevent HVAC circulation of smoke.
Environmental Limits |
|
Temperature: | 32°F to 120°F |
| 0°C to 49°C |
Humidity: | 10% to 93% R.H. |
Air Velocity: | 500 to 4000 Ft/min. |
| 2.54 to 20.3 m/sec. |
Test Features
Magnetic test switch, magnetic reset switch, MOD400R test module (optional), RTS451 Remote Test Station (optional).
Mechanical Specifications |
|
|
Length: | 14.5 inches | 37 cm |
Width: | 5 inches | 13 cm |
Depth (installed): | 4 inches | 10 cm |
Weight: | 4 pounds | 1.8 kg |
Terminals
Captive universal terminal screws with sems plates accept wire sizes of 14 gauge or smaller. The screws can withstand 10
Accessories |
|
|
MOD400R | Sensitivity Test Module | |
RA400Z | Remote Annunciator | |
RTS451/RTS451KEY | Remote Test Station, test & reset switch with alarm LED | |
PA400 | Piezo Sounder | |
APA451 | Annunciator with piezo, alarm & power LEDs | |
Replacement Air Filter (two per package) | ||
Replacement Test Magnet | ||
Replacement End Plug for inlet sampling tube | ||
Replacement Calibrated Test Card (For photo units only) | ||
RS24 | Replacement Screen, Photo | |
Replacement Installation Kit (mounting hardware) | ||
Sampling (Inlet) Tubes |
|
|
TUBE | OUTSIDE DUCT WIDTH | |
1 to 2 feet | (0.3 to 0.6 m) | |
2 to 4 feet | (0.6 to 1.2 m) | |
4 to 8 feet | (1.2 to 2.4 m) | |
8 to 12 feet | (2.4 to 3.7 m) | |
Exhaust Tube Extension |
|
|
5.75 in. (14.6 cm.) additional |
12 |