[2] Figure 1. Exploded view of duct detector components:
| CONDUIT HOLES |
FOAM | INLET SAMPLING TUBE |
GASKETS | (SUPPLIED SEPARATELY) |
TUBE
END
PLUG
DETECTOR BASE
HOUSING
MOUNTING SCREWS
EXHAUST
FILTER ADAPTER
DETECTOR HEAD
SAMPLING TUBE
DUCT DETECTOR
HOUSING
TERMINAL STRIP
PC BOARD
INSULATOR
DUCT DETECTOR
COVER
SAMPLING TUBE
MOUNTING
SCREWS
TEST MAGNET
FILTERS
[3] Contents Of The Duct Detector Kit
1.Complete housing base and cover assembly
2.Two #10 sheet metal mounting screws
3.Two sampling tube filters
4.One test magnet
5.Drilling template
6.Two 5/16
7.Two rubber tube bushing seals
8.Four #6
9.One filter adapter
10.One inlet tube end plug 11.Two #10 speed nuts
NOTE: The inlet sampling tube must be ordered sepa- rately. It must be the correct length for the width of the duct where it will be installed. See Table 1 on page 4 to determine the inlet tube required for different duct widths.
[4] Limitations Of Duct Detectors
WARNING
The National Fire Protection Association has established that DUCT DETECTORS MUST NOT BE USED AS A SUB- STITUTE FOR OPEN AREA DETECTOR PROTECTION as a means of providing life safety. Nor are they a substitute for early warning in a building’s regular fire detection system.
System Sensor supports this position and strongly recom- mends that the user read NFPA Standards 90A, 72, and 101. The DH400ACDCP Air Duct Smoke Detectors are listed per UL 268A.
WARNING
This device will not operate without electrical power. Frequently, fire situations may cause an interruption of power. The system safeguards should be discussed with your local fire protection specialist.
WARNING
This device does not sense smoke unless the ventilation system is operating.
CAUTION
For this detector to function properly, it MUST be installed according to the instructions in this manual. Furthermore, the detector MUST be protected from the elements and operated within ALL electrical and environmental specific- ations listed in this manual. Failure to comply with these requirements may prevent the detector from activating when smoke is present in the air duct.
[5] Installation Sequence |
| |
Step |
| Page |
[5.1] | Verify duct air flow direction and velocity | 2 |
[5.2] | Drill the mounting holes | 3 |
[5.3] | Secure the detector housing to the duct | 3 |
[5.4] | Install the sampling tube | 3 |
[5.5] | Complete the field wiring | 5 |
[5.6] | Install the filters and check pressure differential | 8 |
[5.7] | Perform detector check | 8 |
[5.8] | Install the cover | 8 |
[5.1] Verify Duct Air Flow Direction And Velocity Model DH400ACDCP detectors are designed to be used in air handling systems having air velocities of 500 to 4000
2 |