![B. Installation for Ducts More Than 8 Feet Wide](/images/new-backgrounds/52124/521247x1.webp)
Figure 4. Tube mounting configurations with varying air flow direction and orientation of detector housing. Vertical as well as horizontal mounting is acceptable.
DOTS INDICATE POSITION OF
SAMPLING TUBE HOLES
AIR FLOW | AIR FLOW | |
DIRECTION | ||
DIRECTION | ||
|
DETECTOR HOUSING
INLET
TUBE
DETECTOR
HOUSING
A. |
| B. |
EXHAUST | EXHAUST | INLET |
TUBE | TUBE | TUBE |
HORIZONTAL MOUNTING OF HOUSING
EXHAUST |
|
TUBE | DETECTOR |
| |
| HOUSING |
| EXHAUST |
|
| |
AIR FLOW | TUBE |
| AIR FLOW |
|
|
|
| ||
DIRECTION |
|
| DIRECTION |
|
| INLET | INLET |
|
|
DETECTOR | TUBE | TUBE | D. | |
HOUSING | C. |
|
VERTICAL MOUNTING OF HOUSING
WARNING
In no case should more than 2 air inlet holes be cut off the tube. There must be a minimum of 10 holes in the tube exposed to the air stream.
B. Installation for Ducts More Than 8 Feet Wide
NOTE: To install inlet tubes in ducts more than 8 feet wide, work must be performed inside the air duct. Sampling of air in ducts wider than 8 feet is accom- plished by using the
Install the inlet tube as follows:
1.Drill a
2.Slide the inlet tube with the flange into the right housing bushing. Position the tube so that the arrows point into the air flow. Secure the tube flange to the housing bush- ing with the two #6
3.From inside the duct, couple the other section of the inlet tube to the section already installed using the 1/2- inch conduit fitting supplied. Make sure the holes on both of the air inlet tubes are lined up facing the air flow.
4.Trim the end of the tube protruding through the duct so that 1 to 2 inches of the tube extends outside the duct. Plug this end with the tube end cap and tape closed any holes in the protruding section of the tube. Be sure to seal the duct when the tube protrudes.
5.Any tube (over 3 feet long) that doesn’t protrude through the duct (on the side opposite the housing) must be sup- ported by other means.
NOTE: An alternate method to using the
NOTE: Air currents inside the duct may cause excessive vibration. This vibration can slowly open the seal around the tube and permit air to escape. To prevent this from occurring, a
Modification of Inlet Sampling Tubes
There may be applications where duct widths are not what is specified for the installation. In such cases, it is permis- sible to modify an inlet sampling tube that is longer than necessary to span the duct width.
Use a
4 |