TANDBERG | POWER OUTLET FUSE |
Telepresence T3 | REQUIREMENTS |
Note! The table lists minimum fuse requirements. All electrical work must be done by electricians with local knowledge.
Note! Outside the
On the inside adjacent to the exit there shall be a sign with the following text:
Fire emergency switch is located on the outside of this room.
119076.02 TELEPRESENCE T3 ROOM REQUIREMENTS 12.08
The following minimum power outlet fuse requirements apply to the TANDBERG Telepresence T3:
Item | Watt | Placement | Fuse | On/Off switch |
T1 Module × 3 | 2400 | Back wall | A | 1 |
Presentation | 60 | Back wall | A | 1 |
splitter × 2 |
|
|
|
|
Table power outlet × 6 | 2400 | Back wall | B | 2 |
TCU | 400 | Back wall | C | 2 |
Table quick buttons | 50 | Back wall | C | 2 |
Presentation input | 5 | Back wall | C | 2 |
switch |
|
|
|
|
Touch collaboration | 20 | Back wall | C | 2 |
display splitter |
|
|
|
|
Touch collaboration | 750 | Back wall | C | 2 |
display |
|
|
|
|
Document camera | 300 | Ceiling | D | 2 |
T3 Ceiling mounted | 750 | Ceiling | D | 3 |
lights |
|
|
|
|
T3 LED Module | 1000 | D | 4 | |
Total power | 9335 |
|
|
|