HVAC REQUIREMENTS

TANDBERG

 

Telepresence T3

HVAC REQUIREMENTS

Tip! An average person emits approximately 65 W at rest. You may want to consider this when calculating the HVAC requirements.

Note: Dimensions are between floor and underside of light modules.

119076.02 TELEPRESENCE T3 ROOM REQUIREMENTS 12.08

The following HVAC (heating, ventilation, air-conditioning) requirements apply to the TANDBERG Telepresence T3:

Power consumption System: 1725 W

Power consumption Table: 300 W

Power consumption Lighting: 1300 W

Noise from air-conditioning should be less or equal to 27 dB(A) measured at all seating positions.

Note: The HVAC equipment must not be mounted in a way so that it prevents correct mounting of the ceiling lights and the document camera. Consult the TANDBERG Telepresence T3 Room Installation Guide for more on this.

228 cm 7’534

Make sure that HVAC mounting neither conflicts with the ceiling lights positions nor the document camera position.

A detailed drawing of the ceiling mounting of the lights can be found overleaf, while the drawing 119082 on page 14 shows the position of the document camera.