Table 39 — WSHP Troubleshooting (cont)

 

FAULT

 

HEATING

COOLING

POSSIBLE CAUSE

SOLUTION

Condensate Fault —

 

X

X

Blocked drain

Check for blockage and clean drain.

Code 6

 

 

 

 

 

 

 

 

X

X

Improper trap

Check trap dimensions and location ahead of vent.

 

 

 

 

 

 

 

X

Poor drainage

Check for piping slope away from unit.

 

 

 

 

 

 

Check slope of unit toward outlet.

 

 

 

 

 

 

Poor venting. Check vent location.

 

 

 

 

X

Moisture on sensor

Check for moisture shorting to air coil.

Over/Under Voltage —

 

X

X

Under voltage

Check power supply and 24 vac voltage before and during

Code 7 (Auto Resetting)

 

 

 

 

operation.

 

 

 

 

 

 

Check power supply wire size.

 

 

 

 

 

 

Check compressor starting.

 

 

 

 

 

 

Check 24 vac and unit transformer tap for correct power supply

 

 

 

 

 

 

voltage.

 

 

 

X

X

Over voltage

Check power supply voltage and 24 vac before and during operation.

 

 

 

 

 

 

Check 24 vac and unit transformer tap for correct power supply

 

 

 

 

 

 

voltage.

Performance Monitor —

 

X

 

Heating mode FP2>125 F

Check for poor airflow or overcharged unit.

Code 8

 

 

 

 

 

 

 

 

 

X

Cooling mode FP1>125 F OR

Check for poor water flow or airflow.

 

 

 

 

 

 

 

 

 

FP2< 40 F

 

FP1 and FP2 Thermistors

 

X

 

FP1 temperature is higher

Swap FP1 and FP2 thermistors.

— Code 9

 

 

 

than FP2 temperature.

 

 

 

 

 

X

FP2 temperature is higher

Swap FP1 and FP2 thermistors.

 

 

 

 

 

than FP1 temperature.

 

No Fault Code Shown

 

X

X

No compressor operation

See Scroll Compressor Rotation section.

 

 

 

X

X

Compressor overload

Check and replace if necessary.

 

 

 

X

X

Control board

Reset power and check operation.

Swapped Thermistor —

 

X

X

FP1 and FP2 swapped

Reverse position of thermistors.

Code 9

 

 

 

 

 

 

Unit Short Cycles

 

X

X

Dirty air filter

Check and clean air filter.

 

 

 

X

X

Unit in 'Test Mode'

Reset power or wait 20 minutes for auto exit.

 

 

 

X

X

Unit selection

Unit may be oversized for space. Check sizing for actual load of space.

 

 

 

X

X

Compressor overload

Check and replace if necessary.

Only Fan Runs

 

X

X

Thermostat position

Ensure thermostat set for heating or cooling operation.

 

 

 

X

X

Unit locked out

Check for lockout codes. Reset power.

 

 

 

X

X

Compressor overload

Check compressor overload. Replace if necessary.

 

 

 

X

X

Thermostat wiring

Check Y and W wiring at heat pump. Jumper Y and R for compressor

 

 

 

 

 

 

operation in Test mode.

Only Compressor Runs

 

X

X

Thermostat wiring

Check G wiring at heat pump. Jumper G and R for fan operation.

 

 

 

 

 

 

Check Y and W wiring at heat pump. Jumper Y and R for compressor

 

 

 

 

 

 

operation in test mode.

 

 

 

X

X

Fan motor relay

Jumper G and R for fan operation. Check for line voltage across BR

 

 

 

 

 

 

contacts.

 

 

 

 

 

 

Check fan power enable relay operation (if present).

 

 

 

X

X

Fan motor

Check for line voltage at motor. Check capacitor.

Unit Does Not Operate in

 

 

X

Reversing valve

Set for cooling demand and check 24 vac on RV coil and at control.

Cooling

 

 

 

 

 

 

 

 

 

If RV is stuck, run high pressure up by reducing water flow and while

 

 

 

 

 

 

 

 

 

 

 

 

operating, engage and disengage RV coil voltage to push valve.

 

 

 

 

X

Thermostat setup

Check for 'O' RV setup not 'B'.

 

 

 

 

X

Thermostat wiring

Check O wiring at heat pump. Jumper O and R for RV coil 'Click'.

Insufficient Capacity/

 

X

X

Dirty filter

Replace or clean.

Not Cooling or Heating

 

 

 

 

 

 

X

 

Reduced or no airflow in

Check for dirty air filter and clean or replace.

Properly

 

 

 

 

 

heating

Check fan motor operation and airflow restrictions.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External static too high. Check blower performance per

 

 

 

 

 

 

Tables 11-13.

 

 

 

 

X

Reduced or no airflow in

Check for dirty air filter and clean or replace.

 

 

 

 

 

cooling

Check fan motor operation and airflow restrictions.

 

 

 

 

 

 

 

 

 

 

 

 

External static too high. Check blower performance per

 

 

 

 

 

 

Tables 11-13.

 

 

 

X

X

Leaky ductwork

Check supply and return air temperatures at the unit and at distant duct

 

 

 

 

 

 

registers if significantly different, duct leaks are present.

 

 

 

X

X

Low refrigerant charge

Check superheat and subcooling per Tables 20-30.

 

 

 

X

X

Restricted metering device

Check superheat and subcooling per Tables 20-30. Replace.

 

 

 

 

X

Defective reversing valve

Set for cooling demand and check 24 vac on RV coil and at control.

 

 

 

 

 

 

If RV is stuck, run high pressure up by reducing water flow and while

 

 

 

 

 

 

operating, engage and disengage RV coil voltage to push valve.

 

 

 

X

X

Thermostat improperly located

Check location and for air drafts behind thermostat.

 

 

 

X

X

Unit undersized

Recheck loads and sizing check sensible cooling load and heat pump

 

 

 

 

 

 

capacity.

 

 

 

X

X

Scaling in water heat exchanger

Perform condenser cleaning.

 

 

 

X

X

Inlet water too hot or cold

Check load, loop sizing, loop backfill, ground moisture.

 

LEGEND

 

 

 

 

LED

Light-Emitting Diode

 

 

 

 

RV

Reversing Valve

 

 

 

 

TXV

Thermostatic Expansion Valve

 

 

 

56

Page 56
Image 56
Carrier 50PSH Condensate Fault, Code 7 Auto Resetting, FP1 and FP2 Thermistors, No Fault Code Shown, Only Fan Runs