Carrier PSD006-070 Unit Start-Up Heating Mode, Water Temperature Change Through Heat Exchanger

Models: 50PSH PSV PSD006-070

1 68
Download 68 pages 19.57 Kb
Page 36
Image 36

4.Check the temperature of both supply and discharge water. Compare to Tables 20-30. If temperature is within range, proceed. If temperature is outside the range, check the cooling refrigerant pressures in Tables 20-30.

5.Check air temperature drop across the coil when com- pressor is operating. Air temperature drop should be between 15 and 25 F.

Table 19 — Water Temperature Change

through Heat Exchanger

 

COOLING

HEATING

WATER FLOW RATE (GPM)

RISE (F)

DROP (F)

 

Min

Max

Min

Max

For Closed Loop: Ground Source or

9

12

4

8

Cooling/Boiler Systems at 3 gpm/ton

 

 

 

 

For Open Loop: Ground Water Systems at

20

26

10

17

1.5 gpm/ton

 

 

 

 

Unit Start-Up Heating Mode

NOTE: Operate the unit in heating cycle after checking the cooling cycle. Allow 5 minutes between tests for the pressure or reversing valve to equalize.

1.Turn thermostat to lowest setting and set thermostat switch to HEAT position.

2.Slowly turn the thermostat to a higher temperature until the compressor activates.

3.Check for warm air delivery at the unit grille within a few minutes after the unit has begun to operate.

4.Check the temperature of both supply and discharge water. Compare to Tables 20-30. If temperature is within range, proceed. If temperature is outside the range, check the heating refrigerant pressures in Tables 20-30.

5.Once the unit has begun to run, check for warm air deliv- ery at the unit grille.

6.Check air temperature rise across the coil when compres- sor is operating. Air temperature rise should be between 20 and 30 F after 15 minutes at load.

7.Check for vibration, noise and water leaks.

Table 20 — 50PSH, PSV, PSD006 Typical Unit Operating Pressures and Temperatures

ENTERING

 

FULL LOAD COOLING — WITHOUT HWG ACTIVE

FULL LOAD HEATING — WITHOUT HWG ACTIVE

WATER

Suction

Discharge

Super-

Sub-

Water

Air Temp

Suction

Discharge

Super-

Sub-

Water

Air Temp

WATER

FLOW

TEMP

Pressure

Pressure

heat

cooling

Temp

Drop

Pressure

Pressure

heat

cooling

Temp

Rise

(F)

(GPM/ton)

Rise

Drop

 

(psig)

(psig)

(F)

(F)

(F)

(F) DB

(psig)

(psig)

(F)

(F)

(F)

(F) DB

 

 

 

 

 

 

 

 

 

 

 

 

 

30

1.5

114-124

142-162

24-29

3-8

15.2-17.2

17-23

75-85

272-292

13-18

4-

9

5.9- 7.9

16-22

2.25

111-121

132-152

26-31

3-8

11.4-13.4

17-23

78-88

274-294

13-18

4-

9

4.3- 6.3

16-22

 

3

109-119

122-142

28-33

3-8

7.5-9.5

17-23

81-91

276-296

13-18

4-

9

2.7- 4.7

17-23

50

1.5

130-140

190-210

14-19

2-7

16.5-18.5

18-24

104-114

299-319

12-17

6-11

8.8-10.8

21-27

2.25

129-139

180-200

16-21

2-7

12.3-14.3

18-24

112-122

304-324

12-17

4-

9

6.7- 8.7

22-28

 

3

128-138

170-190

19-24

2-7

8.00-10.0

18-24

120-130

308-328

12-17

3-

8

4.5- 6.5

23-29

70

1.5

143-153

265-285

9-14

2-7

15.5-17.5

18-24

129-139

321-341

11-16

7-12

11.2-13.2

25-31

2.25

141-151

252-272

10-15

2-7

11.5-13.5

18-24

144-154

330-350

13-18

4-

9

8.8- 10.8

27-33

 

3

140-150

240-260

11-16

2-7

7.5-9.5

18-24

159-169

340-360

15-20

3-

8

6.3- 8.3

28-34

90

1.5

149-159

340-370

8-13

2-7

14.2-16.2

17-23

163-173

349-369

13-18

7-12

14.3-16.3

30-36

2.25

149-159

335-355

8-13

2-7

10.6-12.6

17-23

180-190

360-380

11-16

4-

9

11.2-13.2

32-38

 

3

148-158

320-340

8-13

2-7

7.00-9.00

17-23

198-208

372-392

10-15

3-

8

8.1-10.1

34-40

110

1.5

154-164

451-471

8-13

2-7

12.7-14.7

15-21

 

2.25

154-164

428-448

8-13

2-7

9.5-11.5

15-21

 

 

3

153-163

405-425

8-13

2-7

6.5-8.5

15-21

 

LEGEND

DB — Dry Bulb

HWG — Hot Water Generator

No Heating Operation in This Temperature Range

Table 21 — 50PSH, PSV, PSD009 Typical Unit Operating Pressures and Temperatures

ENTERING

 

FULL LOAD COOLING — WITHOUT HWG ACTIVE

FULL LOAD HEATING — WITHOUT HWG ACTIVE

WATER

WATER

Suction

Discharge

Super-

 

Sub-

Water

Air Temp

Suction

Discharge

Super-

Sub-

Water

Air Temp

TEMP

FLOW

 

Temp

Temp

(GPM/ton)

Pressure

Pressure

heat

 

cooling

Rise

Drop

Pressure

Pressure

heat

cooling

Drop

Rise

 

(F)

 

(psig)

(psig)

(F)

 

(F)

(F) DB

(psig)

(psig)

(F)

(F)

(F) DB

 

 

 

 

 

 

 

 

(F)

 

 

 

 

 

(F)

 

 

30

1.5

126-136

161-181

17-22

 

8-13

19.8-21.8

21-27

74-84

278-298

6-11

4-9

6.1-8.1

18-24

 

2.25

126-136

146-166

17-22

 

7-12

14.9-16.9

21-27

77-87

280-300

6-11

4-9

4.5-6.5

18-24

 

 

3

126-136

131-151

17-22

 

6-11

9.9-11.9

21-27

79-89

283-303

6-11

3-8

2.8-4.8

19-25

 

50

1.5

132-142

215-235

10-15

 

8-13

18.8-20.8

20-26

104-114

309-329

8-12

7-12

9.6-11.6

24-30

 

2.25

132-142

200-220

10-15

 

7-12

14.1-16.1

20-26

106-116

312-332

8-12

7-12

7.0-9.0

24-30

 

 

3

132-142

185-205

10-15

 

6-11

9.4-11.4

20-26

108-118

315-335

8-12

7-12

4.5-6.5

25-31

 

70

1.5

138-148

278-298

8-13

 

9-14

17.7-19.7

19-25

127-137

332-352

10-15

10-15

12.0-14.0

29-35

 

2.25

138-148

263-283

8-13

 

8-13

13.1-15.1

19-25

132-142

340-360

11-16

10-15

9.0-10

29-35

 

 

3

137-147

248-268

8-13

 

7-12

8.5-10.5

19-25

138-148

347-367

13-18

10-15

6.1-8.1

30-36

 

90

1.5

142-152

365-385

8-13

 

9-14

16.0-18.0

18-24

164-174

372-392

17-22

13-18

14.5-16.5

35-41

 

2.25

142-152

351-371

8-13

 

8-13

12.0-14.0

18-24

165-175

375-395

18-23

13-18

11.2-13.2

35-41

 

 

3

142-152

337-357

8-13

 

7-12

8.0-10.0

18-24

167-177

379-399

19-24

13-18

7.9-9.9

36-42

 

110

1.5

150-160

439-459

7-12

 

9-14

14.2-16.2

17-23

 

2.25

150-160

439-459

7-12

 

8-13

10.6-12.6

17-23

 

 

3

150-160

439-459

7-12

 

7-12

6.9-8.9

17-23

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

 

DB

Dry Bulb

 

 

 

 

 

 

 

 

 

 

 

 

 

HWG — Hot Water Generator

 

 

 

 

 

 

 

 

 

 

 

 

No Heating Operation in This Temperature Range

 

 

 

 

 

 

 

 

 

36

Page 36
Image 36