DEHUMIDIFICATION MODE — The dehumidification mode setting provides field selection of humidity control. When oper- ating in the normal mode, the cooling airflow settings are deter- mined by the cooling tap setting in Table 11. When dehumidifi- cation is enabled, there is a reduction in airflow in cooling to in- crease the moisture removal of the heat pump. The Dehumidification mode can be enabled in two ways:

1.Constant Dehumidification mode: When the Dehumidifi- cation mode is selected via DIP switch, the ECM will operate with a multiplier applied to the cooling CFM settings (approximately 20 to 25% lower airflow). Any time the unit is running in the Cooling mode, it will oper- ate at the lower airflow to improve latent capacity. The “DEHUM” LED will be illuminated at all times. Heating airflow is not affected.

NOTE: Do not select Dehumidification mode if cooling setting is tap 1.

2.Automatic (humidistat-controlled) Dehumidification mode: When the Dehumidification mode is selected via DIP switch AND a humidistat is connected to termi- nal DH, the cooling airflow will only be reduced when the humidistat senses that additional dehumidification is required. The DH terminal is reverse logic. Therefore, a humidistat (not dehumidistat) is required. The “DEHUM” LED will be illuminated only when the humi- distat is calling for Dehumidification mode. Heating airflow is not affected.

NOTE: Do not select Dehumidification mode if cooling setting is tap 1.

Table 11 — ECM Blower Motor Performance Data

50PS

MAX

FAN

TAP

COOLING MODE

 

DEHUMIDIFICATION MODE

HEATING MODE

 

UNIT

ESP

MOTOR

 

(cfm)

 

 

(cfm)

 

 

(cfm)

 

SETTING

 

 

 

 

 

 

SIZE

(in. wg)

(hp)

Stage 1

Stage 2

 

Fan

Stage 1

Stage 2

Fan

Stage 1

Stage 2

 

Fan

 

 

 

 

 

 

4

750

620

 

380

590

480

380

750

620

 

380

018

0.50

1/2

3

700

570

 

350

550

450

350

700

570

 

350

 

 

 

2

620

510

 

310

480

400

310

620

510

 

310

 

 

 

1

530

430

 

270

530

430

 

270

 

 

 

4

950

780

 

470

740

610

470

1060

870

 

470

024

0.50

1/2

3

850

700

 

420

660

540

420

950

780

 

420

 

 

 

2

730

600

 

360

570

470

360

820

670

 

360

 

 

 

1

610

500

 

300

690

570

 

300

 

 

 

4

1130

920

 

560

880

720

560

1230

1000

 

560

030

0.50

1/2

3

1000

820

 

500

780

640

500

1100

900

 

500

 

 

 

2

880

720

 

440

680

560

440

980

800

 

440

 

 

 

1

750

620

 

380

850

700

 

380

 

 

 

4

1400

1150

 

700

1090

900

700

1400

1150

 

700

036

0.50

1/2

3

1250

1020

 

630

980

800

630

1250

1020

 

630

 

 

 

2

1080

890

 

540

840

690

540

1080

890

 

540

 

 

 

1

900

740

 

450

900

740

 

450

 

 

 

4

1580

1290

 

790

1230

1010

790

1580

1290

 

790

042

0.50

1/2

3

1400

1150

 

700

1100

900

700

1400

1150

 

700

 

 

 

2

1230

1000

 

610

960

790

610

1230

1000

 

610

 

 

 

1

1050

860

 

530

1050

860

 

530

 

 

 

4

1730

1420

 

870

1350

1110

870

1850

1520

 

870

048

0.75

1

3

1550

1270

 

780

1210

990

780

1650

1350

 

780

 

 

 

2

1330

1090

 

670

1040

850

670

1430

1180

 

670

 

 

 

1

1120

920

 

560

1200

980

 

560

 

 

 

4

2050

1680

 

1030

1600

1310

1030

2280

1870

 

1030

060

0.75

1

3

1825

1500

 

910

1420

1170

910

2050

1680

 

910

 

 

 

2

1580

1300

 

790

1230

1010

790

1750

1430

 

790

 

 

 

1

1320

1080

 

660

1470

1210

 

660

 

 

 

4

2230

1780

 

1100

1710

1400

1100

2230

1780

 

1100

070

0.75

1

3

1950

1600

 

980

1520

1250

980

2100

1680

 

980

 

 

 

2

1700

1400

 

850

1330

1090

850

1840

1470

 

850

 

 

 

1

1450

1200

 

730

1520

1220

 

730

LEGEND

ESP — External Static Pressure

NOTES:

1.Factory setting is Tap Setting 2.

2.Airflow is controlled within 5% up to the Max ESP shown with wet coil.

3.Do not select Dehumidification mode if Tap Setting is on Setting 1.

4.All units are ARI/ISO (Air Conditioning & Refrigeration Institute/ International Organization for Standardization) 13256-1 rated Tap Setting 3.

5.Airflow in cfm with wet coil and clean air filter.

6.Units have an ECM (electronically commuted motor) fan motor as a standard feature. The small additional pressure drop of the reheat coil causes the ECM motor to slightly increase rpm to overcome the added pressure drop and maintain selected cfm up to maximum ESP (external static pressure).

7.Unit sizes 006-012 are not available with ECM motors.

30

Page 30
Image 30
Carrier PSD006-070, PSV, 50PSH instruction manual ECM Blower Motor Performance Data, Setting Size