Table 25 — 50PSH, PSV, PSD030 Typical Unit Operating Pressures and Temperatures

ENTERING

 

FULL LOAD COOLING — WITHOUT HWG ACTIVE

 

FULL LOAD HEATING — WITHOUT HWG ACTIVE

WATER

WATER

Suction

Discharge

Super-

Sub-

Water

Air Temp

Suction

Discharge

Super-

Sub-

Water

Air Temp

FLOW

TEMP

Pressure

Pressure

heat

cooling

Temp

Drop

Pressure

Pressure

heat

cooling

Temp

Rise

(F)

(GPM/ton)

Rise

Drop

 

(psig)

(psig)

(F)

(F)

(F)

(F) DB

(psig)

(psig)

(F)

(F)

(F)

 

(F) DB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

116-126

146-166

27-32

7-13

19.6-21.6

16-22

69-

79

275-295

7-12

6-11

7.2-

9.2

16-22

30

2.25

115-125

138-158

27-32

6-11

14.3-16.3

17-23

73-

83

277-297

7-12

6-11

5.4-

7.4

17-23

 

3

115-125

128-148

27-32

6-11

8.0-10.0

17-23

76-

86

279-299

7-12

6-11

3.5-

5.5

17-23

 

1.5

129-139

217-237

12-17

6-11

20.8-22.8

17-23

96-106

300-320

10-15

9-14

10.5-12.5

21-27

50

2.25

128-138

203-223

12-17

5-10

15.0-17.0

18-24

100-110

304-324

10-15

9-14

7.6-

9.6

22-28

 

3

128-138

189-209

12-17

5-10

9.2-11.2

18-24

105-115

309-329

10-15

9-14

4.8- 6.8

22-28

 

1.5

132-142

293-313

9-14

6-11

20.1-22.1

17-23

123-133

327-347

11-16

11-16

13.2-15.2

25-32

70

2.25

131-141

274-294

9-14

5-10

14.4-16.4

18-24

129-139

333-353

11-16

11-16

9.8-11.8

26-33

 

3

131-141

256-276

9-14

5-10

8.6-10.6

18-24

135-145

339-359

11-16

11-16

6.4- 8.4

27-34

 

1.5

137-147

383-403

7-12

5-10

19.4-21.4

16-22

155-165

355-375

13-18

11-16

16.8-18.8

30-38

90

2.25

137-147

362-382

7-12

5-10

13.8-15.8

16-22

162-172

362-382

14-19

11-16

12.7-14.7

31-39

 

3

137-147

342-362

7-12

5-10

8.2-10.2

16-22

169-179

369-389

16-21

11-16

8.6-10.6

32-40

110

1.5

143-153

475-495

6-11

9-14

18.2-20.2

16-22

 

 

2.25

143-153

457-477

6-11

6-11

13.0-14.0

16-22

 

 

 

3

143-153

439-459

6-11

6-11

7.7- 9.7

16-22

 

 

LEGEND

DB — Dry Bulb

HWG — Hot Water Generator

No Heating Operation in This Temperature Range

Table 26 — 50PSH, PSV, PSD036 Typical Unit Operating Pressures and Temperatures

ENTERING

 

FULL LOAD COOLING — WITHOUT HWG ACTIVE

 

FULL LOAD HEATING — WITHOUT HWG ACTIVE

WATER

WATER

Suction

Discharge

Super-

Sub-

Water

Air Temp

Suction

Discharge

Super-

Sub-

Water

Air Temp

FLOW

TEMP

Pressure

Pressure

heat

cooling

Temp

Drop

Pressure

Pressure

heat

cooling

Temp

Rise

(F)

(GPM/ton)

Rise

Drop

 

(psig)

(psig)

(F)

(F)

(F)

(F) DB

(psig)

(psig)

(F)

(F)

(F)

 

(F) DB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

117-127

142-162

33-38

8-14

19.1-21.1

15-22

69-

79

276-296

10-15

10-15

7.2-

9.2

17-23

30

2.25

116-126

134-154

33-38

7-12

13.8-15.8

15-22

73-

83

278-298

10-15

10-15

5.3-

7.3

18-24

 

3

116-126

124-144

33-38

7-12

7.4- 9.4

15-22

76-

86

280-300

10-15

10-15

3.5-

5.5

18-24

 

1.5

136-146

211-231

11-16

6-11

20.6-22.6

17-23

99-109

302-322

10-15

13-18

10.6-12.6

22-28

50

2.25

136-146

197-217

11-16

5-10

14.8-16.8

17-23

103-113

306-326

10-15

13-18

7.7-

9.7

23-29

 

3

136-146

183-203

11-16

5-10

9.0-11.0

17-23

108-118

311-331

10-15

13-18

5.0-

7.0

23-29

 

1.5

137-147

275-295

9-14

10-15

19.0-21.0

18-24

127-137

332-352

10-15

15-20

13.5-15.5

27-34

70

2.25

137-147

260-280

9-14

9-14

13.8-15.8

19-25

133-143

338-358

10-15

15-20

10.1-12.1

28-35

 

3

137-147

245-265

9-14

9-14

8.0-10.0

19-25

139-149

344-364

10-15

15-20

6.7-

8.7

29-36

 

1.5

142-152

373-393

7-12

10-15

19.5-21.5

17-23

164-174

365-385

11-16

15-20

17.4-19.4

34-42

90

2.25

142-152

352-372

8-13

6-11

13.9-15.9

17-23

172-182

372-392

11-16

15-20

13.2-15.2

35-43

 

3

142-152

332-352

8-13

6-11

8.3-10.3

17-23

181-191

379-399

12-17

15-20

9.0-11.0

36-44

110

1.5

147-157

467-487

6-11

10-15

16.2-18.2

16-22

 

 

2.25

147-157

448-468

6-11

8-13

11.9-13.9

16-22

 

 

 

3

147-157

430-450

6-11

7-12

7.6- 9.6

16-22

 

 

LEGEND

DB — Dry Bulb

HWG — Hot Water Generator

No Heating Operation in This Temperature Range

Table 27 — 50PSH, PSV, PSD042 Typical Unit Operating Pressures and Temperatures

ENTERING

 

FULL LOAD COOLING — WITHOUT HWG ACTIVE

 

FULL LOAD HEATING — WITHOUT HWG ACTIVE

 

WATER

WATER

Suction

Discharge

Super-

Sub-

Water

Air Temp

Suction

Discharge

Super-

Sub-

Water

Air Temp

 

FLOW

Temp

Temp

 

TEMP

 

(GPM/ton)

Pressure

Pressure

heat

cooling

Rise

Drop

Pressure

Pressure

heat

cooling

Drop

Rise

 

(F)

 

(psig)

(psig)

(F)

(F)

(F) DB

(psig)

(psig)

(F)

(F)

(F) DB

 

 

 

 

 

 

 

(F)

 

 

 

 

 

 

(F)

 

 

 

30

1.5

114-124

170-190

27-32

10-15

17.2-19.2

17-23

69-

79

286-306

5-10

5-10

4.5-

6.5

16-22

 

2.25

113-123

150-170

27-32

9-14

12.7-14.7

17-23

72-

82

289-309

5-10

6-11

3.9-

5.9

17-23

 

 

3

113-123

131-151

27-32

7-12

8.2-10.2

17-23

75-

85

292-312

6-11

6-11

3.2-

5.2

18-24

 

 

1.5

130-140

226-246

10-15

6-11

17.8-19.8

20-26

100-110

315-335

7-12

6-11

9.0-11.0

22-28

 

50

2.25

129-139

208-228

10-15

5-10

13.3-15.3

20-26

105-115

322-342

8-13

6-11

7.0-

9.0

23-29

 

 

3

129-139

190-210

10-15

4- 9

8.8-10.8

20-26

110-120

330-350

10-15

7-12

5.0-

7.0

24-30

 

 

1.5

132-142

290-310

6-11

6-11

17.3-19.3

19-25

131-141

347-367

11-16

6-11

13.4-15.4

29-35

 

70

2.25

131-141

273-293

6-11

5-10

12.8-14.8

19-25

138-148

358-378

13-18

8-13

10.0-12.0

30-36

 

 

3

131-141

255-275

6-11

4- 9

8.3-10.3

19-25

145-155

369-389

16-21

9-14

6.9-

8.9

31-37

 

 

1.5

136-146

370-390

6-11

6-11

16.0-18.0

17-23

175-185

393-413

19-24

7-12

17.6-19.6

36-42

 

90

2.25

135-145

350-370

6-11

5-10

11.8-13.8

17-23

177-187

401-421

20-25

9-14

13.2-15.2

37-43

 

 

3

135-145

330-350

6-11

4- 9

7.6- 9.6

17-23

180-190

409-429

22-27

12-17

8.7-10.7

38-44

 

110

1.5

143-153

469-489

6-11

6-11

14.0-16.0

16-22

 

 

 

2.25

142-152

448-468

6-11

5-10

11.0-13.0

16-22

 

 

 

 

3

141-151

427-447

6-11

4- 9

7.0- 9.0

16-22

 

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

 

 

DB

Dry Bulb

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HWG — Hot Water Generator

 

 

 

 

 

 

 

 

 

 

 

 

 

No Heating Operation in This Temperature Range

 

 

 

 

 

 

 

 

 

 

 

38

Page 38
Image 38
Carrier 50PSH, PSD006-070, PSV instruction manual Flow