LEGEND

AL

Alarm Relay Contacts

RVS

Reversing Valve Solenoid

ASTAT

Aquastat

TRANS

Transformer

BM

Blower Motor

UPS

Unit Performance Sentinel

BR

Blower Relay

 

 

 

 

 

 

 

 

 

 

Factory Low Voltage Wiring

CB

Circuit Breaker

 

 

 

 

 

 

 

 

 

 

Factory Line Voltage Wiring

CC

Compressor Contactor

 

 

 

 

 

 

 

 

 

 

Field Low Voltage Wiring

CO

Condensate Overflow Sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Field Line Voltage Wiring

COMPR — Compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Printed Circuit Trace

DTS

Discharge Temp Switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Optional Wiring

ECM

Electronically Commutated Motor

 

 

 

 

 

 

 

 

 

 

FP1

Water Coil Freeze Protection Sensor

 

 

 

 

 

 

 

 

 

 

Relay/Contactor Coil

FP2

Air Coil Freeze Protection Sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HP

High-Pressure Switch

 

 

 

 

 

 

 

 

 

 

 

HWG

Hot Water Generator

 

 

 

 

 

 

 

 

 

 

Thermistor

JW

Jumper Wire

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOC

Loss of Charge Pressure Switch

 

 

 

 

 

 

 

 

 

 

Condensate Pan

LWT

Leaving Water Temperature

 

 

 

 

 

 

 

 

 

 

 

MV

Motorized Valve

 

 

 

 

 

 

 

 

 

 

Circuit Breaker

NEC

National Electric Code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P1

Field Wiring Terminal Block

 

 

 

 

 

 

 

 

 

 

Ground

*Optional.

G

Solenoid Coil

Relay Contacts - N.C.

Relay Contacts - N.O.

Capacitor

Temperature Switch

Low Pressure Switch

High Pressure Switch

Wire Nut

Splice Cap

LED

NOTES:

1.Compressor and blower motor thermally protected internally.

2.All wiring to the unit must comply with NEC and local codes.

3.208/230 v transformer will be connected for 208 v operation. For 230 v operation, disconnect RED lead at L1 and attach ORANGE lead to L1. Insulate open end of RED lead. Transformer is energy limiting or may have circuit breaker.

4.FP1 thermistor provides freeze protection for water. When using antifreeze solutions, cut JW3 jumper.

5.Check installation wiring information for specific thermostat hookup. Refer to thermostat installation instructions for wiring to the unit. Thermostat wiring must be “Class 1” and voltage rating equal to or greater than unit supply voltage.

6.24-v alarm signal shown. For dry alarm contact, cut JW1 jumper and dry contact will be available between AL1 and AL2.

7.Transformer secondary ground via Complete C board standoffs and screws to control box. (Ground available from top two standoffs as shown.)

8.Aquastat is supplied with unit and must be wired in series with the hot leg to the pump. Aquastat is rated for voltage up to 277 v.

COMPLETE C CONTROLLER FAULT CODES

DESCRIPTION OF OPERATION

LED

ALARM RELAY

Normal Mode

ON

Open

Normal Mode with UPS Warning

ON

Cycle (Closed 5 Sec.

Open 25 Sec.)

 

 

Complete C is Non-Functional

OFF

Open

Fault Retry

Slow Flash

Open

Lockout

Fast Flash

Closed

Over/Under Voltage Shutdown

Slow Flash

Open

(Closed After 15 Min.)

 

 

Test Mode-No Fault in Memory

Flashing Code 1

Cycling Code 1

Test Mode-HP Fault in Memory

Flashing Code 2

Cycling Code 2

Test Mode-LP Fault in Memory

Flashing Code 3

Cycling Code 3

Test Mode-FP1 Fault in Memory

Flashing Code 4

Cycling Code 4

Test Mode-FP2 Fault in Memory

Flashing Code 5

Cycling Code 5

Test Mode-CO Fault in Memory

Flashing Code 6

Cycling Code 6

Test Mode-Over/Under Shutdown

Flashing Code 7

Cycling Code 7

in Memory

 

 

Test Mode-UPS in Memory

Flashing Code 8

Cycling Code 8

Swapped FP1/FP2 Lockout

Flashing Code 9

Cycling Code 9

Fig. 17 — Units with Complete C ECM Blower, Three-Phase (208/230 V)

16

Page 16
Image 16