Table 39 — WSHP Troubleshooting (cont)
| FAULT | HEATING |
| COOLING | POSSIBLE CAUSE | SOLUTION |
High Head Pressure | X |
|
| Reduced or no airflow in | Check for dirty air filter and clean or replace. | |
|
|
|
|
| heating | Check fan motor operation and airflow restrictions. |
|
|
|
|
|
| |
|
|
|
|
|
| External static too high. Check blower performance per |
|
|
|
|
|
| Tables |
|
|
|
| X | Reduced or no water flow in cool- | Check pump operation or valve operation/setting. |
|
|
|
|
| ing | Check water flow adjust to proper flow rate. See Tables 19 and 31. |
|
|
|
|
|
| |
|
|
|
| X | Inlet water too hot | Check load, loop sizing, loop backfill, ground moisture. |
|
| X |
|
| Air temperature out of range in | Bring |
|
|
|
|
| heating |
|
|
|
|
| X | Scaling in water heat exchanger | Perform condenser cleaning. |
|
| X |
| X | Unit overcharged | Check superheat and subcooling. Reweigh in charge. |
|
| X |
| X | Noncondensables in system | Remove refrigerant, evacuate system and charge unit. |
|
| X |
| X | Restricted metering device | Check superheat and subcooling per Tables |
Low Suction Pressure | X |
|
| Reduced water flow in | Check pump operation or water valve operation/setting. | |
|
|
|
|
| heating | Plugged strainer or filter. Clean or replace. |
|
|
|
|
|
| |
|
|
|
|
|
| Check water flow adjust to proper flow rate. |
|
| X |
|
| Water temperature out of range | Bring water temperature within design parameters. |
|
|
|
| X | Reduced airflow in cooling | Check for dirty air filter and clean or replace. |
|
|
|
|
|
| Check fan motor operation and airflow restrictions. |
|
|
|
|
|
| External static too high. Check blower performance per |
|
|
|
|
|
| Tables |
|
|
|
| X | Air temperature out of range | Too much cold vent air. Bring entering air temperature within design |
|
|
|
|
|
| parameters. |
|
| X |
| X | Insufficient charge | Check for refrigerant leaks. |
Low Discharge Air | X |
|
| Too high airflow | Check blower performance per Tables | |
Temperature in Heating | X |
|
| Poor performance | See “Insufficient Capacity.” | |
High Humidity |
|
| X | Too high airflow | Check blower performance per Tables | |
|
|
|
| X | Unit oversized | Recheck loads and sizing check sensible cooling load and heat pump |
|
|
|
|
|
| capacity. |
Low Refrigerant Suction | X |
|
| Normal operation | Check/compare with Tables | |
Pressure |
|
|
|
|
| |
X |
|
| Reduced water flow | Check pump operation. | ||
|
|
|
| |||
|
|
|
|
|
| Check strainer or filter. |
|
|
|
|
|
| Improper flow regulator. Replace flow regulator. |
|
| X |
|
| Water temperature out of range | Bring water temperature within proper range. |
|
| X |
|
| Scaling in water to refrigerant | Conduct water quality analysis. |
|
|
|
|
| heat exchanger |
|
|
|
|
| X | Reduced airflow | Check for dirty air filter. |
|
|
|
|
|
| Check for dirty air coil. |
|
|
|
|
|
| Check fan motor operation. |
|
|
|
|
|
| External static pressure exceeds fan operating parameters. |
|
| X |
| X | Return air temperature below | Space temperature too cold. Increase space temperature. |
|
|
|
|
| minimum |
|
|
|
|
|
|
| Excessive fresh air. Reduce amount of fresh air exposure. |
|
|
|
| X | Supply air bypassing to return | Check for leaking ductwork. |
|
|
|
|
| airstream (zone systems) |
|
|
| X |
| X | Insufficient refrigerant charge | Locate and repair leak. |
|
| X |
| X | Improperly located TXV sens- | Locate bulb on suction line between reversing valve and compressor. |
|
|
|
|
| ing bulb |
|
|
| X |
| X | Failed or restricted metering | Failed TXV power head, capillary or sensing bulb. Replace. |
|
|
|
|
| device |
|
|
|
|
|
| Plugged TXV strainer. Unplug TXV strainer. | |
|
|
|
|
|
| |
High Refrigerant | X |
| X | Insufficient refrigerant charge | Locate and repair leak. | |
Superheat |
|
|
|
|
| |
X |
| X | Improperly located TXV sens- | Locate bulb on suction line between reversing valve and compressor. | ||
|
|
|
|
| ing bulb |
|
|
| X |
| X | Failed or restricted metering | Failed TXV power head, capillary or sensing bulb. Replace. |
|
|
|
|
| device |
|
|
|
|
|
| Plugged TXV strainer. Unplug TXV strainer. | |
|
|
|
|
|
| |
High Refrigerant | X |
| X | Excessive refrigerant charge | Remove refrigerant as needed. | |
Subcooling |
|
|
|
|
| |
X |
| X | Failed or restricted metering | Failed TXV power head, capillary or sensing bulb. Replace. | ||
|
|
|
|
| device |
|
|
|
|
|
| Plugged TXV strainer. Unplug TXV strainer. | |
|
|
|
|
|
| |
TXV and/or Low Pressure | X |
|
| Normal operation | May occur when entering water temperature is close to minimum. | |
Tubing Frosting |
|
|
|
|
| |
X |
| X | Insufficient refrigerant charge | Locate and repair leak. | ||
|
|
| ||||
|
| X |
| X | Failed or restricted metering | Failed TXV power head, capillary or sensing bulb. Replace. |
|
|
|
|
| device | Plugged TXV strainer. Unplug TXV strainer. |
|
|
|
|
|
| |
Equalizer Line | X |
| X | Failed or restricted metering | Failed TXV power head, capillary or sensing bulb. Replace. | |
Condensing or Frosting |
|
|
| device |
| |
|
|
| Plugged TXV strainer. Unplug TXV strainer. | |||
|
|
|
|
|
| |
| LEGEND |
|
|
|
|
|
LED | — |
|
|
| ||
RV | — Reversing Valve |
|
|
|
|
|
TXV | — Thermostatic Expansion Valve |
|
|
|
57