Advance Data Sheet: Maxeta
TM
iFA Series
©2005 TDK Innoveta Inc.
iFA Advance Datasheet 6/6/2005
(877) 498
-
0099
5/18
Absolute Maximum Ratings:
Stress in excess of Absolute Maximum Ratings may cause permanent damage to the device.
Input Characteristics:
Unless otherwise specified, specifications apply over all Rated Input Voltage, Resistive Load, and Temperature conditions.
Characteristic Min Typ Max Unit Notes & Conditions
Operating Input Voltage 19 24
(28)
#
36 Vdc
When 18V Vin < 19V, the modules will
continue to operate, but the output
voltage regulation may be out of spec at
full load condition
Input Current --- 28.2 37 A Vin = 0 to Vin,max
Input Low End Turn-on Voltage --- 17.9 19 Vdc
Input Low End Turn-off Voltage --- 16.1 19 Vdc
Hysteresis --- 1.8 --- Vdc
Input Over-voltage Turn-off Voltage --- 38.6 --- Vdc
Input High End Turn-on Voltage 36 37.6 --- Vdc
Startup Delay Time from application of input voltage --- 10 --- mS Vo = 0 to 0.1*Vo,nom; on/off =on,
Io=Io,max, Tc=25˚C
Startup Delay Time from on/off --- 8 --- mS Vin = Vin,nom, Io=Io,max, Tc=25˚C
Output Voltage Rise Time --- 42 60* mS Io=Io,max, Vo=0.1 to 0.9*Vo,nom,
Tc=25˚C
Inrush Transient --- --- 1* A
2
S
Input Reflected Ripple --- 5 --- mApp
Vin=Vin,nom, Io=Io,max (0 to 20MHz)
See input/output ripple measurement
figure; BW = 5 MHz
Input Ripple Rejection --- 41 --- dB @120Hz
* Engineering Estimate
#
Telecom 24V battery plant voltage is typically set at 27.24V
Caution: The power modules are not internally fused. An external input line fuse with a maximum value of 40A is required. See the Safety
Considerations section of the data sheet.
Characteristic Min Max Unit Notes & Conditions
Continuous Input Voltage -0.5 40 Vdc
Transient Input Voltage --- 50 Vdc 100mS max.
Isolation Voltage
Input to Output
Input to Base-plate
Output to Base-plate
---
---
---
1500
1500
500
Vdc
Vdc
Vdc
Basic Insulation
Basic Insulation
Operational Insulation
Storage Temperature -55 125 ˚C
Operating Temperature Range (Tc) -40 115* ˚C
Measured at the location specified in the thermal
measurement figure; maximum temperature varies with
output current and module orientation – see curve in the
thermal performance section of the data sheet.