Electrical Specifications

Operating voltages, nominal

-24 Vdc to -48 Vdc

 

 

Current capacity06004-01

20A per bus (40A total for both buses), max. with 20A ce-

 

ramic input fuse (Type ABC)

06004-11

15A per bus (30A total for both buses), max, with 20A ce-

 

ramic input fuse (Type ABC)

 

 

Fuse capacity

20 (ea side)

 

 

Maximum PDU input interruption device rating

25A per bus

 

 

Maximum output interruption device rating

10A GMT fuse

 

 

Maximum continuous output load rating

7A for a 10A fuse

 

 

Alarm contact relay

2A @ 30 Vdc

 

 

Panel heat dissipation per 20A bus

3.9W (13.3 Btu/hr) @ 0% load

 

 

Percentage of full load heat dissipation at nominal voltage

less than 1% of total load wattage

 

 

 

 

 

 

 

 

 

 

 

 

"FAIL SAFE" Applies

 

 

 

20A Input Fuses for Circuits A & B

 

Designation Card Holder

only to Model 06004-11

POWER A

 

 

 

 

POWER B

 

 

A

 

 

 

 

 

 

 

 

 

 

 

FAIL SAFE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

A

B

1

5

10

15

20

1

5

10

15

 

ALARM

20

 

 

 

Circuit A Output

 

 

Circuit B Output

Fuse Alarm LEDs for Circuits A & B

 

 

 

 

 

 

 

 

GMT Fuse Holders

 

 

GMT Fuse Holders

 

 

 

Front View

GMT output fuses are available in capacities ranging from 0.18A to 10A. GMT splash covers are optional for maximum safety when fuses blow. [Visit our website (www.telect.com) or see Page 9 for ordering GMT fuses.] The panel is delivered with “dummy” fuses in all po- sitions.

The standard front panel includes a tri-color fuse alarm LED for each circuit (ALARM A & ALARM B):

The ALARM LEDs are green when all installed input and output fuses are operational.

The ALARM LED is red when any output fuse blows.

The ALARM LED is orange when either of the input fuses blows.

The back contains input and output terminal connections (NEG connections at top; POS RTN connections below), chassis ground con- nections, and wire-wrap pins for external alarm hookups.

Plastic Caps*

CAUTION: DO NOT REVERSE POLARITY

Alarm Pins for Circuits

Screw-Tight, Wire-Clamping

 

A & B

Output Terminals

 

 

 

 

 

 

A

B

A

 

 

FAIL

RELAY

NO C NC NO C NC

-24V

TO -48V

B

RTN

-A -B +A +B

Screw-Tight, Wire-Clamping

Input Terminals

*Plastic caps cover screw-tight terminals used by the manufacturer for installing interior wiring. DO NOT REMOVE CAPS or LOOSEN CLAMPING SCREWS.

Model 06004-01 (Rear View)

Telect, Inc. • USA +1.509.926.6000 • Mexico +52.33.3836.3700

 

Poland +48.713.239.100 • UK +44.1489.889500 • www.telect.com

Page 2

Copyright © 2006 Telect, Inc., All Rights Reserved 130358-2 A0