—— Auxiliary Alarms

Auxiliary alarms are triggered from either an external CO or site source or by the standard alarm relay. Like the standard relay, when triggered, the auxiliary relay is de-energized causing the normally open contacts to close and the normally closed contacts to open.

External Alarm Device

External Alarm Device

External Alarm Device

External Alarm Device

+GND (or POS) NEG (or -GND)

NEG (or -GND) +GND (or POS)

Auxiliary Relay

Contacts

Auxiliary Relay

Trigger

FA AUX RLY

 

 

FA AUX RLY

A

B

FA -24/48V IN*

 

FA -24/48V IN*

FA +GND IN**

 

 

FA +GND IN**

FAIL

 

 

 

RELAY

 

 

 

NO C NC NO C NC

Nomenclature is

 

Internal Wiring

for contacts

 

* NEG (or -GND) trigger.

 

 

 

 

** POS (or +GND) trigger.

a. Separate Alarms for Side A & Side B

External

Alarm Device

External

Alarm Device

+GND (or POS) NEG (or -GND)

Auxiliary Relay

Contacts

Auxiliary Relay

Trigger

FA AUX RLY

 

 

FA AUX RLY

A

B

FA -24/48V IN*

 

FA -24/48V IN*

FA +GND IN**

 

 

FA +GND IN**

FAIL

 

 

 

RELAY

 

 

 

NO C NC NO C NC

Nomenclature is

 

Internal Wiring

for contacts

 

* NEG (or -GND) trigger.

 

 

 

 

** POS (or +GND) trigger.

b. Combined Alarms for Side A & Side B

 

 

External

 

 

 

Alarm Device

 

 

 

 

 

 

 

 

 

 

 

External

 

 

 

Alarm Device

 

 

 

 

+GND (or POS) NEG (or -GND)

 

Auxiliary Relay

FA AUX RLY

 

Contacts

FA AUX RLY

A

Auxiliary Relay

FA -24/48V IN

 

Trigger

FA +GND IN

 

FAIL

RELAY

External

Alarm Device

External

Alarm Device

NEG (or -GND) +GND (or POS)

B

FA -24/48V IN*

FA +GND IN**

NO C NC NO C NC

Nomenclature is

 

for contacts

+GND (or POS)

c. Using the Standard Alarm to Trigger Auxiliary Alarms When a Fuse Blows

Auxiliary Alarm Wiring

Telect, Inc. • USA +1.509.926.6000 • Mexico +52.33.3836.3700 Poland +48.713.239.100 • UK +44.1489.889500 • www.telect.com

Copyright © 2006 Telect, Inc., All Rights Reserved 130358-2 A0

Page 8