DAC and APICONTeledyne API – Model T300/T300M CO Analyzer

Teledyne Analytical Instruments 167
Triggering Events and Data Parameters/Functions for these default channels are:
Name: STBSPN
Event: EXITSP
Report Period: N/A
No. of Records: 200
RS-232 Report: OFF
Channel Enabled: ON
Cal Hold OFF: OFF
Parameters: 2DETMES INST 1OFF
RATIO INST 3OFF
Name: CALDAT
Event: SLPCHG
Report Period: N/A
No. of Records: 200
RS-232 Report: OFF
Channel Enabled: ON
Cal Hold OFF: OFF
Parameters: 3
SLOPE1 INST 3OFF
ZSCNC1 INST 1OFF
OFFSET1 I NST 1OFF
Name: PNUMTC
Event: ATIMER
Report Period: 000:01:00
No. of Records: 360
RS-232 Report: OFF
Channel Enabled: ON
Cal Hold OFF: OFF
Parameters: 2SMPLFLW AVG 1OFF
SMPLPRS AVG 1OFF
Name: STBZERO
Event: EXITZR
Report Period: N/A
No. of Records: 200
RS-232 Report: OFF
Channel Enabled: ON
Cal Hold OFF: OFF
Parameters: 3
RATIO INST 3OFF
STABIL INST 2OFF
DETMES INST 1OFF
Name: CONC
Event: ATIMER
Report Period: 000:01:00
No. of Records: 800
RS-232 Report: OFF
Channel Enabled: ON
Cal Hold OFF: ON
Parameters: 1CONC1 AVG 1OFF
PARAMETER MODE PRECISION STORE NUM
SAMPLES

List of ParametersList of Channels

Name: TEMP
Event: EXITSP
Report Period: 000:06:00
No. of Records: 400
RS-232 Report: OFF
Channel Enabled: ON
Cal Hold OFF: OFF
Parameters: 3
PHTDRV AVG 1OFF
BNTEMP AVG 1OFF
BOXTEMP AVG 1OFF

Figure 7-1: Default DAS Channel Setup