TOA Electronics SSDV-3328 installation instructions Horizontal Vent Figures/Tables, Top Vent

Models: SSDV-3328

1 36
Download 36 pages 20.03 Kb
Page 21
Image 21
HORIZONTAL VENT FIGURES/TABLES

HORIZONTAL VENT FIGURES/TABLES

Notes:

Secure Vent components (rigid vent pipe and terminal) are shown in the Figures; Secure Flex components (flexible vent pipe and terminal) may also be used.

Two 45 degree elbows may be used in place of one 90 degree elbow. The same rise to run ratios, as shown in the venting Figures for 90 elbows,must be followed if 45 degree elbows are used.

SV4.5VF (Secure Vent), SF4.5VF (Secure Flex) firestop/spacer must be used anytime vent pipe passes through a combustible floor or ceil- ing. SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) firestop/spacer must be used anytime vent pipe passes through a combustible wall.

It is very important that the horizontal/inclined run be maintained in a straight (no dips) and recommended to be in a slightly elevated plane, in a direction away from the fireplace of 1/4" rise per foot (20 mm per meter) which is ideal, though rise per foot run ratios that are smaller are acceptable all the way down to at or near level.

The tables show a 1(V) to 5(H) ratio up to a maximum horizontal run of 20 feet except for installations where an elbow is the only vertical vent section in the system (see Figure 35).

AN ELBOW IS ACCEPTABLE AS 1 FOOT OF VERTICAL RISE EXCEPT WHERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE SYSTEM. See Figure 35.

Venting Components Required for Various Exterior Wall Thick-

nesses, when using Square Termination Kit (SV4.5HT-2)

Vent Components Required

Exterior Wall Thickness - inches (mm)

 

 

Termination Kit Only

6 to 9-1/4 (152 to 235)

 

 

Termination Kit and 6 In. Vent

10-3/4 to 14 (273 to 356)

Section (SV4.5L6)

Figure 35 - Top Vent -WARNING

Under no circumstances, may separate sections of concentric flexible vent pipe be joined together.

Table F

H Maximum

 

V Minimum

 

 

 

 

 

feet

(meter)

 

feet

(meter)

3

(0.914)

 

Elbow Only

 

 

 

 

 

Square termination

 

H

(SV4.5HT-2) shown.

 

 

 

V

Flex,

Wall

When using Secure

 

use Firestop/Spacer

 

Firestop/Spacer

SF4.5HF

 

(SV4.5HF)

 

 

See Table 12 as an aid in venting component selection for a particular range of exterior wall thicknesses.

Figure 35 - Top Vent -

ONE 90 DEGREE ELBOW - ELBOW CONNECTION AT APPLIANCE

Termination

Kit and 12 in.

16-3/4 to 20 (426 to 508)

Vent Section (SV4.5L12)

 

Termination

Kit and Tele-

11-3/4 to 20 (299 to 508)

scopic Section (SV4.5L12)

 

 

 

 

Table 12

 

Note: See Figure 33 showing wall thickness range

 

 

when using SV4.5HT-2 termination kit only.

See Table 12 as an aid in venting component selection for a particular range of exterior wall thicknesses.

Table G

H Maximum

V Minimum

 

 

 

 

 

feet

 

(meter)

feet

(meter)

 

 

 

 

 

5

 

(1.524)

1

(0.305)

10

 

(3.048)

2

(0.610)

15

 

(4.572)

3

(0.914)

 

 

 

 

 

20

 

(6.096)

4

(1.219)

 

 

 

 

 

 

V + H = 40 feet (12.2 m) Max.

 

 

H = 20 ft. (6.096 m) Max.

Example: If 20 feet of (H) hori- zontal vent run is needed, then 4 feet minimum of (V) vertical vent will be required.

This table shows a 1(V) to 5(H) ratio. For every 1 foot of vertical, you are allowed 5 feet of (H) horizontal run up to a maximum (H) horizontal run of 20 feet.

H = 28 in. (711 mm) Maximum.

When using Secure Flex,

H

use Firestop/Spacer

 

SF4.5HF

 

Wall Firestop/Spacer (SV4.5HF)

7 in. (178 mm) Manual background

Square termination (SV4.5HT-2) shown.

See Table 12 as an aid in venting component selection for a particular range of exterior wall thicknesses.

Figure 34 - Rear Vent - NO ELBOWS - Square Horizontal Termination (SV4.5HT-2)

Square termination

H

(SV4.5HT-2) shown.

 

When using Secure Flex,

 

use Firestop/Spacer

 

SF4.5VF.

V

When using Secure Flex,

 

use Firestop/Spacer

 

SF4.5HF.

 

Wall Firestop/Spacer

(SV4.5HF)

 

See Table 12 as an aid in venting

Ceiling

Firestop/Spacer

component selection for a particular

(SV4.5VF)

range of exterior wall thicknesses.

 

Figure 36 - Top Vent - ONE 90 DEGREE ELBOW -

ELBOW CONNECTION NOT DIRECTLY AT APPLIANCE

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

21

Page 21
Image 21
TOA Electronics SSDV-3328 installation instructions Horizontal Vent Figures/Tables, Top Vent