The following normally open dry contacts shall be provided through a DB9
male connector located on the rear of the UPS enclosure:
1) UPS On
2) Bypass Active
3) Input Power Loss
4) Battery Voltage Low
D. Battery Test Function
The UPS shall be provided with a “Battery Test” pushbutton to periodically
check the condition of the batteries. Upon detection of a battery problem,
the UPS shall notify the user of this condition allowing the user to perform
a detailed check of the battery string.
*IBM and AS/400 are trademarks of International Business Machine Corporation.
7.0 SERVICE AND WARRANTY
A. Reliability
System mission reliability 200,000** hours and including bypass MTBF
shall be in excess of 3,000,000** (Mean Time Between Failure) hours.
B. Maintainability
Calculated and demonstrated MTTR (Mean Time to Repair) shall be 45
minutes including time to diagnose the problem and replace subassembly.
C. Warranty
The UPS system shall be provided with a comprehensive three-year on-
site warranty (when purchased with a Factory-Authorized Start-up).
The warranty shall cover parts, labor, travel and freight for the UPS. The
battery system has a full two year warranty with remaining years prorata.
Typical on-site response time shall be 4 hours (24 hours maximum). The
warranty period shall expire three years for UPS and two years for the
battery system from date of shipment from manufacturer’s facility.
*Specification subject to change without notices.
**Times are accurate provided normal Preventative Maintenance procedures are
followed.