4200FA-XT
9
UPS Size Dimensions Weight
15 kVA 20”W x 36.3”D x 59.8”H 794-998 lbs.
25 kVA 20”W x 36.3.”D x 59.8”H 804-1,003 lbs.
30 kVA 20”W x 36.3”D x 59.8”H 809-1,008 lbs.
50 kVA 35.25”W x 37.6”D x 59.8”H 1,221-1,946 lbs.
B. Matching Battery Enclosure
The battery cabinet shall consist of a freestanding, matching NEMA1
enclosure equipped with casters and leveling feet. The battery cabinet
shall be provided with necessary hardware to mount cabinet adjacent to
UPS cabinet (if desired). The maximum overall dimensions and weights
shall be as follows:
UPS Size Dimensions Weight Runtime
15 kVA 30”W x 295”D x 59.8”H 1,010 lbs. 21 Min
25 kVA 30”W x 295”D x 59.8”H 1,015 lbs. 10 Min
30 kVA 30”W x 295”D x 59.8”H 1,258 lbs. 13 Min
50 kVA 30”W x 295”D x 59.8”H 1,832 lbs. 13 Min
C. Cable Entry
The UPS shall be provided with cable entry from the rear of the UPS
enclosure.
D. Ventilation and Maintenance Requirements
The UPS shall require the following minimum space for ventilation and
maintenance: 6”(front), 6”(top), 28”(rear), and 20”(side).
6.0 STANDARD FEATURES
A. Emergency Power Off (EPO)
Emergency Power Off (EPO) terminals which trip open the UPS and
battery circuit breakers.
B. RS232 Communication Interface
Serial data link will enable the UPS to interface with a computer to
provide power status and diagnostic information.
C. IBM AS/400* interface