4200FA-XT
5
+/- 3% (loss or return of input power)
+/- 8% (bypass to inverter)
13) Transient Voltage Recovery 50ms maximum to within 2% of nominal
14) Overload Cap. (on inverter) 125% for 90 sec., 150% for 30 sec.
15) Overload Cap. (on bypass) 1000% for 10ms, 125% for 10 min.
16) Crest Factor 3.0
17) Harmonic Voltage Distortion 1.5% THD maximum, 1% maximum for
any single harmonic (linear load)
18) Inrush Current Protection Automatic transfer to bypass, then auto-
return to inverter ( retransfer may be
inhibited by jumper)
19) Output Overcurrent Hall-Effect Current Transformer and
Fusing
C. Batteries
1) Battery Type: Sealed, Valve Regulated Lead Acid cells
2) Protection Time: Each standard matching battery pack shall provide
the minimum run-time:
- 21 minutes back-up time on 15 kVA
- 10 minutes back-up time on 25 kVA
- 13 minutes back-up time on 30 kVA
- 13 minutes back-up time on 50 kVA
3) DC Voltage Range:
UPS Capacity 15 -50kVA
Nominal Voltage 288 VDC
Alarms Voltage (Vlow) 252 VDC
Shutdown Voltage (Vmin) 216 VDC
4) Ripple Voltage: 2% RMS maximum
D. Environmental
1) Efficiency: 86% (AC/AC); 89-90% (DC/AC)
2) Operating Temperature: UPS: 32 to 104° F (0 to 40° C)
Battery: 68 to 77° F (20 to 25° C)
3) Storage Temperature: UPS: -4 to 140° F (-20 to 60° C)
Battery: prolonged storage above 104° F
(40° C) causes rapid battery degradation
4) Relative Humidity: 30-90% (non-condensing)
5) Audible Noise: 60 dB (‘A’ scale @ 1 meter) – 15 / 25 kVA
65 dB (‘A’ scale @ 1 meter) – 30 / 50 kVA