9)Motor Overload Ratio

10)Drive Overload Ratio

11)DBR Overload Ratio

12)Input Power

13)Output Power

14)RR Input Value

15)Peak Load Current

16)Peak Input Voltage

17)Kilowatt Hours

18)Megawatt Hours

B.The drive shall have 320 programmable parameters, which can be changed, while the drive is in run mode.

C.The drive’s 353 parameters shall be adjustable from the 8 key touchpad or computer link.

D.The drive shall be controlled through Palm-Pilot software.

E.The drive’s 11 key touchpad shall be NEMA 12 rated.

F.The drive’s keypad shall be capable of being extended 15 feet from the drive.

G.The drive shall contain a reset of all parameters to factory default settings or user defaults (whichever one is chosen).

H.The drive shall have an elapsed time meter and will save the past four faults in memory.

2.8Optional features

A.12-pulse diode rectification for maximum harmonics attenuation shall be available for 460V drives 25HP through 100HP.

B.Pneumatic interface (3-15psi) transducers are available upon request.

C.Isolated input and output transducers are available upon request.

D.All drives regardless of size/voltage should have isolated bypass capability as an available option.

E.600V, E3 drives are also available from 5HP to 125HP. The ratings shall be 540V-660V/60 Hz for 600V models.

Communication options to include:

1)Metasys, N2 Interface

2)Landis-Steaffa, P1 Interface

3)RS485

4)Modbus RTU

5)Modbus+

6)Devicenet

7)AB RIO

8)Profibus DP

9)Lonworks

6