4.2 Electrical Operation
Electrical operations are performed as shown in the flow diagram below.
Circuit breaker OPEN
Control power applied
Motor begins operating ・Springs begin tightening
Springs Charged・Motor stops
CLOSE signal given
CLOSE coil energized
・Spring status changes to yellow ・CLOSE operation standby
Circuit breaker CLOSED
Auxiliary relay closes
OPEN signal given
OPEN/TRIP coil energized
Circuit breaker OPEN
Spring changes to white and switching status changes to ON
Motor begins operating
・Spring begins tightening
Spring taut・Motor stops
Spring status changes to yellow
Switching status changes to OFF
Next CLOSE operation is NOT possible until the CLOSE signal is canceled.
- 19 -