7. Network Characteristics Configuration
The
Communication Method:
SW1 # | Function | |
1 | ||
|
OFF |
| Modbus RTU (factory default) | |||
ON |
| Modbus ASCII | |||
Baud Rate: |
|
| |||
|
|
|
| ||
| SW1 # |
| Function | ||
4 | 3 | 2 | |||
| |||||
|
|
|
| ||
OFF | OFF | OFF | 300 baud | ||
OFF | OFF | ON | 600 baud | ||
OFF | ON | OFF | 1200 baud | ||
OFF | ON | ON | 2400 baud | ||
ON | OFF | OFF | 4800 baud | ||
ON | OFF | ON | 9600 baud (factory default) | ||
ON | ON | OFF | 19.2 kbaud | ||
ON | ON | ON | 38.4 kbaud | ||
Parity: |
|
|
|
| |
|
|
| |||
SW1 # |
| Function | |||
6 | 5 |
| |||
|
| ||||
|
|
| |||
OFF | OFF | even parity (factory default) | |||
OFF | ON | odd parity | |||
ON | OFF | no parity (2 stop bits) | |||
ON | ON | no parity (1 stop bit) - applies only to RTU mode |
Protocol: |
| |
|
| |
SW1 # | Function | |
7 | ||
|
OFF | Modicon Modbus (factory default) | |
ON | DO NOT SELECT (reserved for future expansion) | |
Station Number Origin: (refer to section 8) | ||
|
| |
SW1 # | Function | |
8 | ||
| ||
|
| |
OFF | Drive A’s inverter number parameter (factory default) | |
ON | Switch SW2 address setting | |
| 11 |