Toshiba T1-40 PLC manual Gateway Modes, Gateway Setup, Specifications

Models: T1-40 PLC

1 4
Download 4 pages 37.63 Kb
Page 3
Image 3
♦Gateway Modes

Gateway Modes

There are two communications ports on the Gateway, labeled PLC1 and PLC2. Each port can be configured for either RS232 or RS485 operation. Gateway can communicate through either the T-Series RS232 programming port or the RS485 computer link port.

Gateway Setup

Gateway is setup using simple MS Windows setup software. The software allows devices/registers from one device to be mapped to devices/registers of the other device. For Modbus, the 400001 numbered holding registers can be mapped directly to D data registers in the Toshiba PLC.

In the above example, 5 data registers in the T1 PLC starting at D101 are written into PID controller modbus registers starting with holding register 400001. 3 Holding registers in the PID controller are written into the data registers of the T1 starting at D0 (D0 –D2). It is also possible to control the priority and frequency of the data transfer using the Gateway setup software.

Specifications

Power Supply:

24 VDC +/- 5 % (50 ma MAX.) No Fuse inside

 

5 VDC +/- 5 % FROM PLC (120 ma MAX.)

Communication:

Two ports as follows:

 

Com 1: RS232C/RS485

 

Com 2: RS232C/RS485

Status LEDs:

PLC1 LED

 

STATUS LED

Temperature:

PLC2 LED

Operating: 0 to 60 °C Storage: - 40 to 90 °C

Humidity:

10% to 90% (Non condensing)

Immunity to ESD:

Level 3 as per IEC1000-4-2

Immunity to Transients:

Level 3 as per IEC1000-4-4

Radiated Susceptibility:

Level 3 as per IEC1000-4-3

Emissions:

EN55011 CISPR A

Dimensions:

97mm(W) X 15.mm (H) X 42mm(D) DIN RAIL mounting

 

available

Weight:

100 gm Approx.

Page 3

Page 3
Image 3
Toshiba T1-40 PLC manual Gateway Modes, Gateway Setup, Specifications