If the EOI is already connected via the RS485/RS232 channel, then no change is required.
6.Connect the drive’s common serial communication port (CNU2) to one of the channels (A, B or C) of the
7.Reinstall the drive’s front cover / close the drive’s cabinet door.
8.Repeat steps 1, 2, 4, 5, 6 and 7 to connect other drives as needed.
9.Connect the Ethernet network cable to the shielded RJ45 connector marked “Network” on the bottom of the unit. If a ground cable is going to be used, attach the ground cable to the screw terminal marked “GND” on the bottom side of the unit (refer to section 4). Ensure that the network cable is fully seated into the modular connector, and route the cable such that it is located well away from any drive input power or motor wiring. Also take care to route the cable away from any sharp edges or positions where it may be pinched.
10.Take a moment to verify that the
11.Turn the power sources to all connected drives ON, and verify that the drives function properly. If the drives do not appear to power up, or do not function properly, immediately turn power OFF. Repeat steps 1 and 2 to remove all power from the drives. Then, verify all connections. Contact ICC or your local drive distributor or manufacturer for assistance if the problem persists.
3.2 Installation for S7, S9 and A7 Drives
1.
CAUTION! Verify that all input power sources to the drives to be connected have been turned OFF and are locked and tagged out.
2.
DANGER!
Wait at least 5 minutes for the drive’s electrolytic capacitors to discharge before proceeding to the next step. Do not touch any internal parts with power applied to the drive, or for at least 5 minutes after power to the drive has been removed. A hazard exists temporarily for electrical shock even if the source power has been removed. Verify that the CHARGE LED has gone out before continuing the installation process.
3.Attach the mounting clip and unit enclosure in your desired manner (refer to page 11 for more information).