Installer’s Guide

CHECKOUT PROCEDURE

After installation has been completed, it is recommended that the entire system be checked against the following list:

1.

Refrigerant Line, Leak checked

[

]

2.

Suction Lines and Fittings properly insulated

[

]

3.

Have all Refrigerant Lines been secured and

 

 

 

isolated properly?

[

]

4.Have passages through masonry been sealed? If mortar is used, prevent mortar from coming

 

into direct contact with copper tubing

[

]

5.

Verify tightness of all electrical connects

[

]

6.

Observe outdoor fan during on cycle for clearance

 

 

 

and smooth operation

[

]

7.

Indoor coil drain line drains freely. Pour water

 

 

 

into drain pan

[

]

8.

Supply registers and return grilles open and

 

 

 

unobstructed

[

]

9.

Return air filter installed

[

]

10.Thermostat thermometer is accurate. Check against a reliable thermometer. Adjust per

 

instructions with thermostat

[

]

11.

Is correct speed tap being used?

 

 

 

(Indoor blower motor)

[

]

12.

Operate complete system in each mode to

 

 

 

insure safe operation

[

]

TROUBLESHOOTING CHART — WHAT TO CHECK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.

 

 

 

REF

 

 

 

*

 

 

 

 

 

 

 

 

 

 

 

CONTROL

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

WHAT

HIGH

 

 

 

 

 

 

 

 

 

 

 

.

 

 

 

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DEFROST

 

 

 

 

 

 

 

 

 

LOW

 

 

 

STUCK

REF

 

 

AIR

 

 

CIR

SOVCHECK

 

 

 

 

 

 

 

 

 

CONTACTOR

 

 

LOW

 

EXCESSIVE

RES

 

 

 

 

 

DEFROST

 

 

TO

 

 

 

 

 

 

 

 

 

REF

 

 

TXV

RES .

 

 

 

 

 

 

 

START

 

 

 

 

 

 

 

.

 

 

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.

 

 

 

 

 

.

 

 

COIL

 

 

 

 

POWERVOLTAGE

RUN

 

 

VOLTAGE

 

 

 

INEFFICIENT

 

 

O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I

 

 

 

VALVE

 

 

 

 

 

 

CONTACTOR

 

 

 

.

 

 

 

.

 

SOV

 

 

SYSTEM FAULTS CHECK COMPRESSOR

START

 

 

 

 

VOLTAGE

 

 

 

.

 

 

.

 

 

 

 

CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NONCONDENSABLESSTUCK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

 

EVAP

RECIRCULATIONRESTRICTIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

UNDERCHARGE.

RELAY

 

 

 

 

 

 

 

 

 

 

 

THERMOSTATCOMPRESSOROVERCHARGE

 

 

SUPERHEAT

 

DEFECTIVE

 

 

 

 

 

 

CAPACITORCAPACITORCONTACTS

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

SUPPLYWIRING

 

 

RELAY

WIRING

 

 

FUSE COMP

 

 

 

AIRFLOWLEAKINGLEAKING

 

 

 

MODE

 

IOL

 

 

 

 

 

LOAD

 

 

OPEN

 

 

 

 

 

DEFDEF

 

 

 

 

 

 

 

 

 

 

 

COIL

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

. .

REFRIGERANT CIRCUIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Head Pressure Too High

 

C

 

 

 

 

 

 

 

 

 

 

 

 

P

P

S

P

S

 

 

 

S

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

P

P

S

 

 

 

 

P

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Head Pressure Too Low

 

C

 

 

 

 

 

 

 

 

 

 

 

S

P

 

 

 

 

 

S

S

 

S

S

S

P

 

 

H

 

 

 

 

 

 

 

 

 

 

 

S

P

 

 

 

 

 

S

S

 

S

S

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Suction Pressure Too High

 

C

 

 

 

 

 

 

 

 

 

 

 

S

P

P

 

 

 

 

S

 

 

P

 

P

 

 

H

 

 

 

 

 

 

 

 

 

 

 

S

 

 

 

 

 

 

 

S

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Suction Pressure Too Low

 

C

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

 

 

 

S

P

S

 

S

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

S

S

 

S

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid Refrig. Floodback (TXV)

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

 

 

P

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid Refrig. Floodback

 

C

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

S

S

 

S

P

 

 

 

 

 

(Cap. Tube)

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

S

S

 

S

 

 

 

S

 

 

I.D. Coil Frosting

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

S

S

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Runs

 

 

C

 

 

 

 

 

 

 

 

 

 

 

S

P

 

S

S

 

 

 

S

P

S

S

S

S

 

Inadequate or No Cooling/Htg

 

H

 

 

 

 

 

 

 

 

 

 

 

S

P

 

 

S

 

 

 

S

P

S

S

 

S

 

ELECTRICAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor & O.D. Fan

 

C

P

P

 

 

 

 

 

S

P

S

P

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Won’t Start

 

 

H

P

P

 

 

 

 

 

S

P

S

P

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Will Not Start

 

C

 

P

S

P

S

S

S

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

But O.D. Fan Runs

 

 

H

 

P

S

P

S

S

S

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O.D. Fan Won’t Start

 

C

 

P

 

P

 

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

P

 

P

 

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Hums But Won’t Start

 

C

 

 

 

P

S

S

S

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

P

S

S

S

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Cycles on IOL

 

C

 

P S P S S S

 

 

 

 

P S P P S

 

S S

 

S

 

 

S

 

 

 

 

H

 

P S P S S S

 

 

 

 

P S P P S

 

S

 

 

S P

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I.D. Blower Won’t Start

 

C

P

P

 

 

 

 

 

S

P

S

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

P

P

 

 

 

 

 

S

P

S

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DEFROST

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Won’t Initiate

Defrost

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P

P

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defrost Terminates on Time

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Icing Up

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

S

S

 

 

S

 

 

P

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C - Cooling

H - Heating

P - Primary Causes

 

S - Secondary Causes

* - 3 Phase Only

 

 

 

 

 

 

 

 

 

 

 

Literature Order Number

2TWA2-IN-1A

P.I.

 

 

 

File Number

SV-UN-S/S-2TWA2-IN-1A 9/02

 

 

 

 

 

 

 

 

 

 

Supersedes

2TWA2-IN-1 4/02

 

 

 

 

 

 

 

 

 

 

Stocking Location

PI Louisville & Webb/Mason - Houston

 

Trane

 

 

 

 

 

 

A business of

Trane has a policy of continuous product and product data improvement and it reserves the right to change

 

American Standard Companies

 

www.trane.com

design and specifications without notice.

 

Page 8
Image 8
Trane 2TWA0, 2TWA2 manual Checkout Procedure, Troubleshooting Chart What to Check