Installer’s Guide
CHECKOUT PROCEDURE
After installation has been completed, it is recommended that the entire system be checked against the following list:
1. | Refrigerant Line, Leak checked | [ | ] |
2. | Suction Lines and Fittings properly insulated | [ | ] |
3. | Have all Refrigerant Lines been secured and |
|
|
| isolated properly? | [ | ] |
4.Have passages through masonry been sealed? If mortar is used, prevent mortar from coming
| into direct contact with copper tubing | [ | ] |
5. | Verify tightness of all electrical connects | [ | ] |
6. | Observe outdoor fan during on cycle for clearance |
|
|
| and smooth operation | [ | ] |
7. | Indoor coil drain line drains freely. Pour water |
|
|
| into drain pan | [ | ] |
8. | Supply registers and return grilles open and |
|
|
| unobstructed | [ | ] |
9. | Return air filter installed | [ | ] |
10.Thermostat thermometer is accurate. Check against a reliable thermometer. Adjust per
| instructions with thermostat | [ | ] |
11. | Is correct speed tap being used? |
|
|
| (Indoor blower motor) | [ | ] |
12. | Operate complete system in each mode to |
|
|
| insure safe operation | [ | ] |
TROUBLESHOOTING CHART — WHAT TO CHECK
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| O |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| . |
|
|
| REF |
|
|
| * |
|
|
|
|
|
|
|
|
|
|
| CONTROL |
|
|
|
|
|
|
| D |
|
|
|
|
|
|
|
|
| ||||
| WHAT | HIGH |
|
|
|
|
|
|
|
|
|
|
| . |
|
|
| . |
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| DEFROST |
| |||||||||
|
|
|
|
|
|
|
| LOW |
|
|
| STUCK | REF |
|
| AIR |
|
| CIR | SOVCHECK |
|
|
| ||||||
|
|
|
|
|
| CONTACTOR |
|
| LOW |
| EXCESSIVE | RES |
|
|
|
|
| DEFROST |
| ||||||||||
| TO |
|
|
|
|
|
|
|
|
| REF |
|
| TXV | RES . |
|
|
| |||||||||||
|
|
|
| START |
|
|
|
|
|
|
| . |
|
| . |
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
| . |
|
|
|
|
| . |
|
| COIL |
|
|
| |||||
| POWERVOLTAGE | RUN |
|
| VOLTAGE |
|
|
| INEFFICIENT |
|
| O |
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
| I |
|
|
| VALVE |
|
| |||||||||||
|
|
|
| CONTACTOR |
|
|
| . |
|
|
| . |
| SOV |
|
| |||||||||||||
SYSTEM FAULTS CHECK COMPRESSOR | START |
|
|
|
| VOLTAGE |
|
|
| . |
|
| . |
|
|
|
| CONTROL |
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| NONCONDENSABLESSTUCK |
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
| TRANSFORMER |
|
| EVAP | RECIRCULATIONRESTRICTIONS |
|
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
| UNDERCHARGE. | RELAY |
| |||||||||||||||||
|
|
|
|
|
|
|
|
|
| THERMOSTATCOMPRESSOROVERCHARGE |
|
| SUPERHEAT |
| DEFECTIVE |
| |||||||||||||
|
|
|
|
| CAPACITORCAPACITORCONTACTS |
|
|
|
|
|
|
| AIRFLOW |
|
| ||||||||||||||
|
|
| SUPPLYWIRING |
|
| RELAY | WIRING |
|
| FUSE COMP |
|
|
| AIRFLOWLEAKINGLEAKING |
| ||||||||||||||
|
| MODE |
| IOL |
|
|
|
|
| LOAD |
|
| OPEN |
|
|
|
|
| DEFDEF | ||||||||||
|
|
|
|
|
|
|
|
|
|
| COIL | . |
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| . . | ||
REFRIGERANT CIRCUIT |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Head Pressure Too High |
| C |
|
|
|
|
|
|
|
|
|
|
|
| P | P | S | P | S |
|
|
| S |
|
|
|
| ||
| H |
|
|
|
|
|
|
|
|
|
|
|
| P | P | S |
|
|
|
| P | S |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
Head Pressure Too Low |
| C |
|
|
|
|
|
|
|
|
|
|
| S | P |
|
|
|
|
| S | S |
| S | S | S | P |
| |
| H |
|
|
|
|
|
|
|
|
|
|
| S | P |
|
|
|
|
| S | S |
| S | S |
| P |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
Suction Pressure Too High |
| C |
|
|
|
|
|
|
|
|
|
|
| S | P | P |
|
|
|
| S |
|
| P |
| P |
| ||
| H |
|
|
|
|
|
|
|
|
|
|
| S |
|
|
|
|
|
|
| S |
|
| P |
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
Suction Pressure Too Low |
| C |
|
|
|
|
|
|
|
|
|
|
|
| P |
|
|
|
|
|
| S | P | S |
| S |
|
| |
| H |
|
|
|
|
|
|
|
|
|
|
|
| P |
|
|
| S | S |
| S |
| S |
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
Liquid Refrig. Floodback (TXV) |
| C |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| P |
|
|
|
|
| P |
| |
| H |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| P |
|
|
|
|
| P |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
Liquid Refrig. Floodback |
| C |
|
|
|
|
|
|
|
|
|
|
|
| P |
|
| S | S |
| S | P |
|
|
|
|
| ||
(Cap. Tube) |
|
| H |
|
|
|
|
|
|
|
|
|
|
|
| P |
|
| S | S |
| S |
|
|
| S |
|
| |
I.D. Coil Frosting |
|
| C |
|
|
|
|
|
|
|
|
|
|
|
| P |
|
|
| S | S |
|
|
|
|
|
|
|
|
|
| H |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Compressor Runs |
|
| C |
|
|
|
|
|
|
|
|
|
|
| S | P |
| S | S |
|
|
| S | P | S | S | S | S |
|
Inadequate or No Cooling/Htg |
| H |
|
|
|
|
|
|
|
|
|
|
| S | P |
|
| S |
|
|
| S | P | S | S |
| S |
| |
ELECTRICAL |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Compressor & O.D. Fan |
| C | P | P |
|
|
|
|
| S | P | S | P | P |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Won’t Start |
|
| H | P | P |
|
|
|
|
| S | P | S | P | P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Compressor Will Not Start |
| C |
| P | S | P | S | S | S |
|
|
|
| P |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
But O.D. Fan Runs |
|
| H |
| P | S | P | S | S | S |
|
|
|
| P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
O.D. Fan Won’t Start |
| C |
| P |
| P |
|
| S |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| H |
| P |
| P |
|
| S |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
Compressor Hums But Won’t Start |
| C |
|
|
| P | S | S | S |
|
|
|
| P |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| H |
|
|
| P | S | S | S |
|
|
|
| P |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
Compressor Cycles on IOL |
| C |
| P S P S S S |
|
|
|
| P S P P S |
| S S |
| S |
|
| S |
|
|
| ||||||||||
| H |
| P S P S S S |
|
|
|
| P S P P S |
| S |
|
| S P |
| S |
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||
I.D. Blower Won’t Start |
| C | P | P |
|
|
|
|
| S | P | S |
| S |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| H | P | P |
|
|
|
|
| S | P | S |
| S |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
DEFROST |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Unit Won’t Initiate | Defrost |
| C |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| H |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| P | P | P | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
Defrost Terminates on Time |
| C |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| H |
|
|
|
|
|
|
|
|
|
|
|
| P |
|
|
|
|
|
|
|
|
|
|
|
| P | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
Unit Icing Up |
|
| C |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| H |
|
|
|
|
|
|
|
|
|
|
|
| P |
|
|
| S | S |
|
| S |
|
| P |
| P | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
C - Cooling | H - Heating | P - Primary Causes |
| S - Secondary Causes | * - 3 Phase Only |
|
|
|
|
|
|
|
|
|
|