Installation
Low Voltage Wiring
Controls Using 24 VAC
Before installing any wire, refer to the electrical access locations on the unit submittals located on pages 7 through 9.
Ensure that the AC control wiring be- tween the controls and the unit’s ter- mination point does not exceed three
(3)ohms/conductor for the length of the run.
Note: Resistance in excess of
Check all loads and conductors for grounds, shorts, and
Use copper conductors unless other- wise specified.
Do not run the AC low voltage wiring in the same conduit with the high volt- age power wiring.
Table 4: 24V AC conductors
Distance | Recommended |
from unit to Control | Wire Size |
18 gauge | |
16 gauge | |
14 gauge | |
|
|
Low voltage connection diagrams are shown in Figure 9. Optional desuper- heater fuse installation shown in Fig- ure 10.
Table 5: Deluxe controller diagnostic LEDs
Figure 9: Low voltage connection
Figure 10: Desuperheater fuse installation
Color: Green
LED1
OFF
ON
ON
ON
FLASH
ON
ON
ON
ON
ON
ON
Color: Red |
| Controller Mode | |
|
|
| |
LED2 | LED3 |
| |
|
| ||
OFF | OFF | Control OFF | |
OFF | OFF |
| Normal/Compressor OFF |
| |||
OFF | FLASH | ||
OFF | ON |
| Normal/Compressor ON |
| |||
ON | OFF | Brownout Condition | |
FLASH | ON |
| Soft Lockout (low pressure) |
| |||
FLASH | FLASH | Soft Lockout (high pressure) | |
ON | ON |
| Manual Lockout (low pressure) |
| |||
ON | FLASH | Manual Lockout (high pressure) | |
FLASH | OFF |
| Manual Lockout (condensate overflow) |
| |||
ON | OFF | Compressor Disable | |
|
|
|
|
17 |