Trane WPWD Troubleshooting Checklist, Problem No response to any thermostat setting, Heating

Models: GSWD WPWD EXWA

1 31
Download 31 pages 50.77 Kb
Page 28
Image 28
Problem

Problem

No response to any thermostat setting

Unit short cycles

Insufficient capacity

High pressure switch open

High head pressure

Low suction pressure

Low Pressure switch open

Freezestat open

Troubleshooting

Checklist

Heating

Cooling

Cause

Correction

X

X

Main power off

Check fuses

X

X

Defective control transformer

Replace

X

X

Broken or loose connection

Repair

X

X

Defective thermostat

Replace

X

X

Transformer

Reset Transformer

X

X

Thermostat or sensor improperly located

Relocate

X

X

Low on refrigerant charge

Locate leak, repair and recharge by

weight (not by superheat)

 

 

 

X

X

Restricted thermal expansion valve

Replace

X

X

Defective reversing valve

See WSHP-IOM-# for touch test chart

X

X

Thermostat improperly located

Relocate

X

X

Unit undersized

Recalculate heat gains/losses

X

X

Inadequate water flow

Increase GPM

X

X

Scaling in heat exchanger

Clean or replace

 

X

Water too hot

Decrease temperature

X

 

Water too cold

Increase temperature

 

X

Inadequate GPM

Increase water flow to unit

 

X

Water too hot

Decrease temperature

X

X

Overcharged with refrigerant

Decrease charge

X

X

Defective pressure switch

Check or replace

 

X

Trash in heat exchanger

Backflush

 

X

Low water flow

Increase GPM

X

X

Overcharge of refrigerant

Decrease charge

X

X

Non-condensable in system

Evacuate and recharge by weight

X

X

Water too hot

Decrease temperature

X

X

Undercharged

Locate leak, repair and recharge

X

X

Restricted thermal expansion valve

Repair / replace

X

 

Inadequate GPM

Increase GPM

X

 

Inadequate GPM

Increase GPM

X

 

Water too cold

Increase temperature

X

X

Undercharged with refrigerant

Increase charge

X

X

Defective pressure switch

Replace

 

 

 

Raise water temperature. For smaller

X

X

Heat transfer fluid too cold

tonnage units, switch pressure switch

 

 

 

wires from 35 psig to 7 psig

X

 

Inadequate GPM

Increase GPM

X

 

Water too cold

Increase GPM

X

X

Defective freezestat

Replace freezestat

 

 

 

Replace freezestat. For smaller tonnage

X

 

Heat transfer fluid too cold

units, switch pressure wires from 35 psig

 

 

 

to 7 psig.

28

WSHP-SVX02A-EN

Page 28
Image 28
Trane WPWD Troubleshooting Checklist, Problem No response to any thermostat setting, Unit short cycles, Heating, Cooling