Problem
No response to any thermostat setting
Unit short cycles
Insufficient capacity
High pressure switch open
High head pressure
Low suction pressure
Low Pressure switch open
Freezestat open
Troubleshooting
Checklist
Heating | Cooling | Cause | Correction | |
X | X | Main power off | Check fuses | |
X | X | Defective control transformer | Replace | |
X | X | Broken or loose connection | Repair | |
X | X | Defective thermostat | Replace | |
X | X | Transformer | Reset Transformer | |
X | X | Thermostat or sensor improperly located | Relocate | |
X | X | Low on refrigerant charge | Locate leak, repair and recharge by | |
weight (not by superheat) | ||||
|
|
| ||
X | X | Restricted thermal expansion valve | Replace | |
X | X | Defective reversing valve | See | |
X | X | Thermostat improperly located | Relocate | |
X | X | Unit undersized | Recalculate heat gains/losses | |
X | X | Inadequate water flow | Increase GPM | |
X | X | Scaling in heat exchanger | Clean or replace | |
| X | Water too hot | Decrease temperature | |
X |
| Water too cold | Increase temperature | |
| X | Inadequate GPM | Increase water flow to unit | |
| X | Water too hot | Decrease temperature | |
X | X | Overcharged with refrigerant | Decrease charge | |
X | X | Defective pressure switch | Check or replace | |
| X | Trash in heat exchanger | Backflush | |
| X | Low water flow | Increase GPM | |
X | X | Overcharge of refrigerant | Decrease charge | |
X | X | Evacuate and recharge by weight | ||
X | X | Water too hot | Decrease temperature | |
X | X | Undercharged | Locate leak, repair and recharge | |
X | X | Restricted thermal expansion valve | Repair / replace | |
X |
| Inadequate GPM | Increase GPM | |
X |
| Inadequate GPM | Increase GPM | |
X |
| Water too cold | Increase temperature | |
X | X | Undercharged with refrigerant | Increase charge | |
X | X | Defective pressure switch | Replace | |
|
|
| Raise water temperature. For smaller | |
X | X | Heat transfer fluid too cold | tonnage units, switch pressure switch | |
|
|
| wires from 35 psig to 7 psig | |
X |
| Inadequate GPM | Increase GPM | |
X |
| Water too cold | Increase GPM | |
X | X | Defective freezestat | Replace freezestat | |
|
|
| Replace freezestat. For smaller tonnage | |
X |
| Heat transfer fluid too cold | units, switch pressure wires from 35 psig | |
|
|
| to 7 psig. |
28 |