Electrical Data
and Connections
Compressor Motor Electrical Data (60 Hertz)
| NominalVoltage | 200 | 230 | 380 | 460 | 575 |
Compressor | Voltage | 180/ | 208/ | 342/ | 414/ | 516/ |
Code | Utilization Range | 220 | 254 | 418 | 506 | 633 |
| Max kW | 174 | 174 | 174 | 174 | 174 |
B1, B2 | RLA @ Max kW | 557 | 484 | 291 | 241 | 193 |
| LRAY | 970 | 818 | 488 | 400 | 329 |
| LRAD | 3103 | 2617 | 1561 | 1280 | 1053 |
| Max kW | 249 | 249 | 249 | 249 | 249 |
C1, C2 | RLA @ Max kW | 812 | 698 | 421 | 349 | 279 |
| LRAY | 1173 | 936 | 558 | 469 | 375 |
| LRAD | 3634 | 2901 | 1727 | 1453 | 1162 |
| Max kW | 329 | 329 | 329 | 329 | 329 |
D1, D2 | RLA @ Max kW | 888 | 888 | 549 | 455 | 367 |
| LRAY | 1690 | 1532 | 850 | 730 | 612 |
| LRAD | 5477 | 4966 | 2755 | 2366 | 1984 |
|
|
|
|
|
|
|
Notes:
1. See Selection Procedure Section for details.
2.The RLA @ Max kW is based on the performance of the motor developing full rated horsepower.
3.Electrical component sizing should be based on actual jobsite operating conditions.This factor can be obtained through the use of the Series R chiller selection program available through localTrane sales offices.
Compressor Motor Electrical Data (50 Hertz)
| NominalVoltage | 380 | 400 | 415 |
Compressor | Voltage | 342/ | 360/ | 374/ |
Code | Utilization Range | 418 | 440 | 457 |
| Max kW | 139 | 145 | 148 |
B1, B2 | RLA @ Max kW | 233 | 233 | 233 |
| LRAY | 391 | 412 | 428 |
| LRAD | 1229 | 1296 | 1348 |
| Max kW | 201 | 209 | 213 |
C1, C2 | RLA @ Max kW | 349 | 349 | 349 |
| LRAY | 456 | 480 | 498 |
| LRAD | 1414 | 1488 | 1544 |
| Max kW | 271 | 280 | 284 |
D1, D2, D3 | RLA @ Max kW | 455 | 455 | 455 |
| LRAY | 711 | 748 | 776 |
| LRAD | 2303 | 2424 | 2515 |
| Max kW | 288 | 301 | 306 |
E3 | RLA @ Max kW | 488 | 488 | 488 |
| LRAY | 711 | 748 | 776 |
| LRAD | 2303 | 2424 | 2515 |
Notes:
1. See Selection Procedure Section for details.
2.The RLA @ Max kW is based on the performance of the motor developing full rated horsepower.
3.Electrical component sizing should be based on actual jobsite operating conditions.This factor can be obtained through the use of the Series R chiller selection program available through localTrane sales offices.
Electrical Connections
Starter Panel | Selection | Lug Size |
Connection | RLA | |
Terminals Only | (2) | |
| (4) | |
Main Circuit | (1) | |
Breaker or | (2) | |
(2) | ||
Disconnect Switch | (2) | |
| (4) |
Note:
1. Lug sizes are independent of starter type.
19 |