Trane RTHD manual Electrical Data and Connections, Electrical Connections

Models: RTHD

1 32
Download 32 pages 59.58 Kb
Page 19
Image 19
Electrical Data

Electrical Data

and Connections

Compressor Motor Electrical Data (60 Hertz)

 

NominalVoltage

200

230

380

460

575

Compressor

Voltage

180/

208/

342/

414/

516/

Code

Utilization Range

220

254

418

506

633

 

Max kW

174

174

174

174

174

B1, B2

RLA @ Max kW

557

484

291

241

193

 

LRAY

970

818

488

400

329

 

LRAD

3103

2617

1561

1280

1053

 

Max kW

249

249

249

249

249

C1, C2

RLA @ Max kW

812

698

421

349

279

 

LRAY

1173

936

558

469

375

 

LRAD

3634

2901

1727

1453

1162

 

Max kW

329

329

329

329

329

D1, D2

RLA @ Max kW

888

888

549

455

367

 

LRAY

1690

1532

850

730

612

 

LRAD

5477

4966

2755

2366

1984

 

 

 

 

 

 

 

Notes:

1. See Selection Procedure Section for details.

2.The RLA @ Max kW is based on the performance of the motor developing full rated horsepower.

3.Electrical component sizing should be based on actual jobsite operating conditions.This factor can be obtained through the use of the Series R chiller selection program available through localTrane sales offices.

Compressor Motor Electrical Data (50 Hertz)

 

NominalVoltage

380

400

415

Compressor

Voltage

342/

360/

374/

Code

Utilization Range

418

440

457

 

Max kW

139

145

148

B1, B2

RLA @ Max kW

233

233

233

 

LRAY

391

412

428

 

LRAD

1229

1296

1348

 

Max kW

201

209

213

C1, C2

RLA @ Max kW

349

349

349

 

LRAY

456

480

498

 

LRAD

1414

1488

1544

 

Max kW

271

280

284

D1, D2, D3

RLA @ Max kW

455

455

455

 

LRAY

711

748

776

 

LRAD

2303

2424

2515

 

Max kW

288

301

306

E3

RLA @ Max kW

488

488

488

 

LRAY

711

748

776

 

LRAD

2303

2424

2515

Notes:

1. See Selection Procedure Section for details.

2.The RLA @ Max kW is based on the performance of the motor developing full rated horsepower.

3.Electrical component sizing should be based on actual jobsite operating conditions.This factor can be obtained through the use of the Series R chiller selection program available through localTrane sales offices.

Electrical Connections

Starter Panel

Selection

Lug Size

Connection

RLA

L1-L3 (Each Phase)

Terminals Only

000-760

(2) #4-500 MCM

 

761-888

(4) 4/0-500 MCM

Main Circuit

000-185

(1) #4-350 MCM

Breaker or

186-296

(2) 2/0-250 MCM

Non-Fused

297-444

(2) 3/0-350 MCM

Disconnect Switch

445-592

(2) #1-500 MCM

 

593-888

(4) 4/0-500 MCM

Note:

1. Lug sizes are independent of starter type.

RLC-PRC020-EN

19