period three

The Compressor in a System

notes

+RW￿*DV￿%\SDVV￿WR￿(YDSRUDWRU￿,QOHW

H[SDQVLRQ￿YDOYH

HYDSRUDWRU

OLTXLG￿OLQH

KRW￿JDV

 

 

E\SDVV￿YDOYH

GLVWULEXWRU

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FRQGHQVHU

 

 

VXFWLRQ￿OLQH

 

 

 

FRPSUHVVRU

RLO￿UHWXUQ￿OLQH

 

 

Figure 49

Hot gas bypass may be another solution for preventing evaporator frosting in DX applications. Hot gas bypass diverts hot, high-pressure refrigerant vapor from the discharge line to the low-pressure side of the refrigeration system. This added “false load” helps to maintain an acceptable suction pressure and temperature. Hot gas bypass, however, fails to reduce energy consumption because it does not allow the compressor to shut off at these low load conditions.

In a DX application, there are two bypass methods used. The first method bypasses refrigerant vapor from the compressor discharge line to the inlet of the evaporator coil. Sensing a decrease in suction pressure, a pressure- actuated valve opens to bypass hot refrigerant vapor from the compressor discharge line to the inlet of the evaporator coil, between the expansion valve and the liquid distributor. This increases the rate at which liquid refrigerant is boiled off within the evaporator coil and causes the temperature of the refrigerant leaving the coil to rise. Sensing this increased temperature, the expansion valve feeds additional refrigerant to the coil, increasing the suction pressure and temperature.

The principal advantage of hot gas bypass to the evaporator inlet is that the refrigerant velocity in the evaporator and suction line is higher at low loads. This promotes a uniform movement of oil through the evaporator coil and suction piping. When the evaporator is located above the compressor, as shown, the holdup of oil within the vertical hot-gas-bypass riser must be considered. Since the flow rate within the hot-gas-bypass line modulates over a wide range, no size of pipe can ensure adequate velocity to carry oil up the riser. Oil will collect at the base of the vertical riser when the bypass valve throttles to lower flow rates. This problem is commonly addressed by adding a small oil return line between the base of the riser and the suction line.

TRG-TRC004-EN

35

Page 42
Image 42
Trane TRG-TRC004-EN manual +Rw*Dv%\Sdvvwrydsrudwru,Qohw