UH-SVX01A-EN 47
Hot Water Performance Data
Performance based on 200°F (93°C) EWT, 60°F (16°C) E.A.T., 20°F (11°C)TD.
For Fan Diameter see Pages 41 and 42.
* For the lower output, an optional Speed Controller must be ordered.
†Stated AMP is full load for standard motors. AMP draw varies by motor manufacturer ± 0.2 AMPS. Please see your unit's motor data plate for exact (FLA) Full Load Amp rating.
120 87,100
(25.5)
8.8
(.555)
102
(39)
0.39
(.119)
1/3
(.249)
1140 1900
(.897)
900
(4.572)
4.5 III
132 95,800
(28.1)
9.6
(.606)
104
(40)
0.41
(.125)
1/3
(.249)
1140 2000
(.944)
950
(4.826)
4.5 IV
144 104,000
(30.5)
10.4
(.656)
104
(40)
0.43
(.131)
1/3
(.249)
1140 2200
(1.038)
1000
(5.080)
4.5 IV
156 113,000
(33.1)
11.3
(.713)
100
(38)
0.53
(.162)
1/3
(.249)
1140 2600
(1.227)
1150
(5.842)
4.5 IV
180 118,000
(34.6)
11.8
(.744)
110
(43)
0.6
(.183)
1/3
(.249)
1140 2200
(1.038)
800
(4.064)
4.5 III
204 148,000
(43.4)
14.9
(.940)
107
(42)
0.79
(.241)
1/3
(.249)
1140 2900
(1.369)
1000
(5.080)
4.5 IV
240 174,000
(51.0)
17.4
(1.098)
106
(41)
1.06
(.323)
1/3
(.249)
1140 3500
(1.652)
900
(4.572)
4.5 IV
280 209,100
(61.3)
21.0
(1.325)
106
(41)
1.33
(.405)
1/2
(.373)
1100 4200
(1.982)
980
(4.978)
5.4 IV
300 230,000
(67.4)
23.0
(1.451)
102
(39)
2.1
(.640)
1/2
(.373)
1100 5000
(2.360)
700
(3.556)
5.4 IV
360 261,300
(76.6)
26.2
(1.653)
103
(39)
2.1
(.640)
1/2
(.373)
1100 5500
(2.596)
1000
(5.080)
5.4 IV
Table 30. Hot Water Calculations and Correction Factors S Type
EXAMPLE:
UNIT SIZE: __________________ 024
Entering Water Temp. _______ 160°F
Entering Air Temp. ___________ 40°F
Water Temperature Drop _______ 10°F
I. CAPACITY @ 20° TD:
A. For 200° EWT, 60° EAT
Read output directly from Table 29, 17,400
BTU/HR (Ref., Std. 024)
B. For EWT and/or EAT above or below
Standard
Multiply output from Table 29 by factor from
Table 31
17,400 x .878 = 15,277 BTU/HR.
II. CAPACITY AT OTHER TD's
A. For TD's from 5 to 60°F
Multiply output obtained in IA. Or IB. (above)
by appropriate factor from Table 32
IA-17,400 x 1.15 = 20,010 BTU/HR.
-OR-
IB-15,277 x 1.15 = 17,569 BTU/HR.
III. GPM AT OTHER TD's
A. For TD's from 5 to 60°F
Multiply GPM of unit for 20° TD, from
Table 29 by appropriate factor from Ta ble 32
1.8 x 2.30 = 4.14 GPM (Applies only to units
with Std. 200° EWT, 60° EAT.) For all others
calculate using formula-GPM = BTU/500 x TD
IV. CAPACITY AT OTHER RATES OF
WATER FLOW
Multiply output from Table 29 by factor from
Table 34.
V. PRESSURE LOSS AT OTHER TD's
A. For TD's from 5 to 60°F
Multiply P.D. of unit for 20°TD, from Table 2 9
by appropriate factor from the Table 32
.014 x 5.00 = .07 Ft. H2O
Table 29. Model S Serpentine and Header Type (continued)