Hot Water Performance Data

Table 36. Low Output Units Standard Vertical Unit with All Air Ports Open** (continued)

 

Water

 

 

 

Final

 

 

 

 

 

 

Temp.

 

 

Press. Drop

Air.

 

 

Nominal

Outlet

 

 

Drop

Output MBH

Flow Rate

ft/water

Temp.

 

 

CFM

Velocity

 

Model No. °F (°C)

(kW)

G.P.M. (L/s)

m/water

°F (°C)

Motor H.P. (kW)

R.P.M. (m3/s)

FPM (m/s)

Sound Rating

 

20°

310.5

32.00

4.23

90.5°

 

 

 

 

 

500L

(11.1°)

(91.0)

(2.019)

(1.290)

(32.5)

1-1/2

1160

9380

1860

IV

 

 

 

 

 

 

(1.119)

 

(4.377)

(9.449)

 

 

30°

281.7

19.35

1.67

87.7°

 

 

 

 

 

 

 

 

 

(16.7°)

(82.5)

(1.221)

(.509)

(30.9)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10°

394.4

54.19

6.83

95.3°

 

 

 

 

 

 

(5.6°)

(115.6)

(3.418)

(2.083)

(35.2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

600L

20°

377.0

38.85

3.68

93.7°

1-1/2

1160

10,300

2060

IV

(11.1°)

(110.5)

(2.451)

(1.122)

(34.3)

 

(1.119)

 

(4.807)

(10.465)

 

 

 

 

 

 

 

 

 

 

30°

342.2

23.51

1.45

90.6°

 

 

 

 

 

 

(16.7°)

(100.3)

(1.483)

(.442)

(32.6)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20°

453.7

46.76

4.11

95.1°

 

 

 

 

 

720L

(11.1°)

(132.9)

(2.950)

(1.254)

(35.1)

3

1165

11,900

2380

IV

 

 

 

 

 

 

(2.237)

 

(5.553)

(12.090)

 

 

30°

411.7

28.28

1.62

91.9°

 

 

 

 

 

 

 

 

 

(16.7°)

(120.6)

(1.784)

(.494)

(33.3)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**Performance based on 200° EWT, 20° T.D., 60° E.A.T. Performance at 10° & 30° T.D. is also shown. For capacities at other conditions, use the correction multipliers in the tables on page 17.

*Speed controller option is required for reduced ratings.

Table 37. HOT WATER CALCULATIONS AND CORRECTION FACTOR P STYLE

 

 

EXAMPLE:

 

 

UNIT SIZE _________________042

 

 

Entering Water Temp. _____160°F

 

 

Entering Air Temp. ________ 40°F

 

 

Water Temperature Drop ____ 10°F

 

 

 

I. CAPACITY @ 20° TD:

Read output directly from Table 35 & Table 36,

 

A. For 200° EWT, 60° EAT

22,700 BTU/HR (Ref., Std. 042, p. 12).

 

 

 

 

B. For EWT and/or EAT above or below

Multiply output from Table 35 & Table 36 by factor from

22,700 x .878 = 19,931 BTU/HR.

Standard

Table 38.

 

 

 

 

II. CAPACITY AT OTHER TD's

Multiply output obtained in IA. or IB.

IA - 22,700 x 1.15 = 26,105 BTU/HR.

A. For TD's from 5 to 60°F

(above) by appropriate factor from Table 39

-OR-

 

 

IB - 19,931 x 1.15 = 22,921 BTU/HR.

III.GPM AT OTHER TD's A. For TD's from 5 to 60°F

Multiply GPM of unit for 20° TD, from Table 35 & Table 36 by appropriate factor from Table 39

2.34x 2.30 = 5.38 GPM (Applies only to units with. Std. 200° EWT, 60° EAT.) For all others calculate using formula - GPM = BTU/500 x TD

IV. PRESSURE LOSS AT OTHER TD's

Multiply P.D. of unit for 20° TD, from Table 35 & Table 36 .06 x 5.00 = .30 Ft. H2O

A.ForTD's from 5 to 60°F

by appropriate factor from Table 39

 

 

UH-SVX01A-EN

53

Page 53
Image 53
Trane UH-SVX01A-EN manual HOT Water Calculations and Correction Factor P Style, Capacity @ 20 TD, II. Capacity AT Other TDs

UH-SVX01A-EN specifications

The Trane UH-SVX01A-EN is an advanced unit ventilator designed to provide efficient and reliable heating, cooling, and ventilation in various commercial and educational applications. This unit is particularly engineered for use in schools, offices, and healthcare facilities, ensuring optimal indoor air quality while maintaining energy efficiency.

One of the main features of the UH-SVX01A-EN is its innovative design that incorporates cutting-edge technologies for enhanced performance. The unit is equipped with a high-efficiency fan and motor system that operates quietly while delivering consistent airflow. This ensures a comfortable environment for occupants without the disruptive noise common in traditional ventilation systems.

Another standout characteristic of the UH-SVX01A-EN is its versatility. It offers multiple configuration options, allowing it to be tailored to meet specific building requirements and occupant needs. The unit can be integrated with various control systems, including advanced building management systems, which provide precise temperature control and enhance energy savings.

The use of variable air volume technology allows the UH-SVX01A-EN to adjust airflow rates based on real-time occupancy and environmental conditions. This intelligent airflow management not only improves comfort but also significantly reduces energy consumption, aligning with sustainable building practices.

Additionally, Trane has incorporated a range of filtration options within the unit, which contribute to improved indoor air quality by capturing dust, allergens, and other airborne particulates. This makes the UH-SVX01A-EN an ideal choice for settings where air purity is paramount, such as healthcare environments.

Maintenance of the UH-SVX01A-EN is also user-friendly, with easy access to key components for servicing and inspections. Trane's commitment to reliability and efficiency is manifested in the durable materials and construction of this unit, ensuring longevity and lower lifetime operational costs.

In summary, the Trane UH-SVX01A-EN combines advanced technology, versatile configurations, and a focus on energy efficiency and indoor air quality. This unit ventilator is designed to meet the demands of modern buildings while supporting environmental sustainability initiatives. With its robust features and flexible integration options, the UH-SVX01A-EN stands out as a reliable solution for any commercial heating, cooling, and ventilation needs.