UH-SVX01A-EN 53
Hot Water Performance Data
**Performance based on 200° EWT, 20° T.D., 60° E.A.T. Performance at 10° & 30° T.D. is also shown. For capacities at other conditions, use the correction multipliers in the
tables on page 17.
*Speed controller option is required for reduced ratings.
500L
20°
(11.1°)
310.5
(91.0)
32.00
(2.019)
4.23
(1.290)
90.5°
(32.5) 1-1/2
(1.119)
1160 9380
(4.377)
1860
(9.449)
IV
30°
(16.7°)
281.7
(82.5)
19.35
(1.221)
1.67
(.509)
87.7°
(30.9)
600L
10°
(5.6°)
394.4
(115.6)
54.19
(3.418)
6.83
(2.083)
95.3°
(35.2)
1-1/2
(1.119)
1160 10,300
(4.807)
2060
(10.465)
IV
20°
(11.1°)
377.0
(110.5)
38.85
(2.451)
3.68
(1.122)
93.7°
(34.3)
30°
(16.7°)
342.2
(100.3)
23.51
(1.483)
1.45
(.442)
90.6°
(32.6)
720L
20°
(11.1°)
453.7
(132.9)
46.76
(2.950)
4.11
(1.254)
95.1°
(35.1) 3
(2.237)
1165 11,900
(5.553)
2380
(12.090)
IV
30°
(16.7°)
411.7
(120.6)
28.28
(1.784)
1.62
(.494)
91.9°
(33.3)
Table 37. HOT WATER CALCULATIONS AND CORRECTION FACTOR P STYLE
EXAMPLE:
UNIT SIZE _________________042
Entering Water Temp. _____160°F
Entering Air Temp. ________ 40°F
Water Temperature Drop ____ 10°F
I. CAPACITY @ 20° TD:
A. For 200° EWT, 60° EAT
Read output directly from Table 35 & Ta ble 36,
22,700 BTU/HR (Ref., Std. 042, p. 12).
B. For EWT and/or EAT above or below
Standard
Multiply output from Table 35 & Table 36 by factor from
Tabl e 38 .
22,700 x .878 = 19,931 BTU/HR.
II. CAPACITY AT OTHER TD's
A. For TD's from 5 to 60°F
Multiply output obtained in IA. or IB.
(above) by appropriate factor from Table 39
IA - 22,700 x 1.15 = 26,105 BTU/HR.
-OR-
IB - 19,931 x 1.15 = 22,921 BTU/HR.
III. GPM AT OTHER TD's
A. For TD's from 5 to 60°F
Multiply GPM of unit for 20° TD, from Table 35 & Ta ble 36
by appropriate factor from Table 39
2.34 x 2.30 = 5.38 GPM (Applies only
to units with. Std. 200° EWT, 60° EAT.)
For all others calculate using formula -
GPM = BTU/500 x TD
IV. PRESSURE LOSS AT OTHER TD's
A.ForTD's from 5 to 60°F
Multiply P.D. of unit for 20° TD, from Table 3 5 & Tab le 3 6
by appropriate factor from Table 39
.06 x 5.00 = .30 Ft. H2O
Table 36. Low Output Units Standard Vertical Unit with All Air Ports Open** (continued)
Model No.
Water
Temp.
Drop
°F (°C)
Output MBH
(kW)
Flow Rate
G.P.M. (L/s)
Press. Drop
ft/water
m/water
Final
Air.
Temp.
°F (°C) Motor H.P. (kW) R.P.M.
Nominal
CFM
(m3/s)
Outlet
Velocity
FPM (m/s) Sound Rating