Trion T5200 V. Replacement Parts Ordering Information, Vi. Warranty, Vii. Troubleshooting Guide

Models: T5200

1 15
Download 15 pages 25.35 Kb
Page 6
Image 6
Wash Ionizing/ Collecting Cells

Wash Ionizing/ Collecting Cells

WARNING:

DO NOT USE HIGH PRESSURE STEAM CLEANING EQUIPMENT TO CLEAN CELLS. THE EXCESSIVE HEAT AND PRESSURE WILL CAUSE THE PLATES TO WARP AND IN TURN POSSIBLY CAUSE EXCESSIVE ARCING.

1.Turn the control switch “OFF” and disconnect power to the unit.

2.Open the cell access door.

3.Remove ionizer/collector cells and wash in HOT detergent water. If the collected contaminant is of extremely dry nature, it can be blown off the cells with a pressure hose or gently tapping the end plate of the cell.

4.Remove the mechanical pre-filter. Remove collected dust or lint by vacuuming or brushing. Wash with warm, soapy water.

5.Rinse all components thoroughly in warm, clear water and allow to drip dry completely.

6.Replace pre-filter and ionizer/collector cells. ENSURE the airflow arrows point in the direction of airflow (towards the blower).

7.Close the access door; reconnect power to the unit.

8.Turn control switch to “ON”. If arcing occurs or the indicating light flickers, the components may still be damp. Turn the unit OFF and allow the cells to dry completely.

Inspections

The motor and blower on Trion T5200 air cleaners have sealed ball bearings and never need lubricating.

Belt tension should be checked periodically. When a moderate force is applied to the belt midway between the pulleys, the belt should deflect approximately ½ “.

CAUTION

Having too much tension on the belts will shorten the belt life and place undue stress on the motor and blower bearings.

V. REPLACEMENT PARTS ORDERING INFORMATION

The following pages contain exploded views and Bills of Material for the Trion T Series Air Cleaners. Use these pages to determine the part numbers of the items needed. To order parts contact your local Trion representative and provide the following information:

a.Unit Model number – located on the data label near the junction box.

b.Part Number and description – from exploded views.

VI. WARRANTY

All Trion Electronic Air Cleaners are warranted for 3 Year Limited Warranty on units and 1 Year Limited Warranty on replacement parts. Labor is NOT included. Do not return defective parts without permission from the factory and receiving a material return acceptance number.

VII. TROUBLESHOOTING GUIDE

T5200 Problems and Possible Causes:

1.Indicating Light Out

a.Unit not plugged in

b.Control switch “Off”

c.Cell access panel not fully closed

d.Broken cell insulator

e.Extremely dirty cells

f.Service panel not secured in place

2.Excessive arcing noise after washing

a.Collector elements still wet – Allow more drying time

b.See “Continuous arcing noise” below

3.Continuous arcing noise and flickering indicating light

a.Extremely dirty collector plates

b.Bent collector plates

c.Large piece of material lodged between cell plates

4.Contaminant Bypass

a.Velocity of airflow is too high through unit

b.Collector plates not grounded

6

Page 6
Image 6