12R

Service

If you are returning your Inverter/Charger to Tripp Lite, please pack it carefully, using the ORIGINALPACKING MATERIALthat came

with the unit. Enclose a letter describing the symptoms of the problem. If the Inverter/Charger is within the warranty period, enclose a copy

of your sales receipt. To obtain service you must obtain a Returned Material Authorization (RMA) number from Tripp Lite or an authorized

Tripp Lite service center.

Your Inverter/Charger requires no maintenance and contains no user-serviceable or replaceable parts, but should be kept dry at all times.

Periodically check, clean and tighten all cable connections, as necessary, both at the unit and at the battery.

Try these remedies for common Inverter/Charger problems before calling for assistance. Call Tripp Lite Customer Service at (773) 869-1234

before returning your unit for service.

MaintenanceTroubleshooting
SYMPTOM PROBLEMS CORRECTIONS
No AC Output Unit is not properly connected to utility power Connect unit to utility power.
(All Indicator Lights are OFF) Operating Mode Switch is set to “OFF”and AC input Set Operating Mode Switch to “AUTO/REMOTE”or “CHARGE ONLY”.
is present.
This is normal when the Operating Mode Switch is set to No correction is required.AC output will return when AC input
“CHARGE ONLY”and AC input is absent. returns.Set Operating Mode Switch to “AUTO/REMOTE”if you
require AC output.
Circuit breaker is tripped. Reset circuit breaker.
Unit has shut down due to battery overcharge (preventing Disconnect any auxiliary chargers.Reset by moving Operating Mode
battery damage).The problem may be with connected Switch to “OFF”.Wait 1 minute and switch to “AUTO/REMOTE”or
auxiliary chargers, if any, or with the unit’s charger. “CHARGE ONLY.”If unit remains in shutdown mode after several
attempts to reset, contact Tripp Lite Customer Service for assistance.
Unit has shut down due to excessive battery discharge. Use an auxiliary charger* to raise battery voltage.Check external
battery connections and fuse.Unit automatically resets when
condition is cleared.
Unit has shut down due to overload. Reduce load.Reset by moving Operating Mode Switch to “OFF”.
Wait 1 minute.Switch to “AUTO/REMOTE”or “CHARGE ONLY”.
Battery Not Recharging Connected batteries are dead. Check and replace old batteries.
(AC Input Present) Battery fuse* is blown. Check and replace fuse.*
Battery cabling* is loose. Check and tighten or replace cabling.*
Unit has shut down due to battery overcharge (preventing Disconnect any auxiliary chargers.Reset by moving Operating Mode
battery damage).The problem may be with connected Switch to “OFF”.Wait 1 minute and switch to “AUTO/REMOTE”or
auxiliary chargers, if any, or with the unit’s charger. or “CHARGE ONLY.”If unit remains in shutdown mode after several
attempts to reset, contact Tripp Lite Customer Service for assistance.
Input circuit breaker is tripped. Reset circuit breaker.
All Three Battery Indicator Lights Battery is excessively discharged. Use an auxiliary charger* to raise battery voltage.Check external
Are Slowly Flashing. battery connections and fuse.Unit automatically resets when
(½ Second Flashes) condition is cleared.
All Three Battery Indicator Lights Battery is overcharged.Unit will shut down to prevent Disconnect any auxiliary chargers.Reset by moving Operating Mode
Are Rapidly Flashing battery damage.The problem may be with connected auxiliary Switch to “OFF”.Wait 1 minute and switch to “AUTO/REMOTE”or
(¼ Second Flashes) chargers, if any, or with the unit’s charger. “CHARGE ONLY.”If unit remains in shutdown mode after several
attempts to reset, contact Tripp Lite Customer Service for assistance.
Red “LOW”Battery Battery voltage is low. Unit will automatically shut down Make sure that AC power is present in order to recharge batteries.
Indicator Light Is Flashing after 5 seconds to protect battery from damage. Reset by moving Operating Mode Switch to “OFF then to
“AUTO/REMOTE”or “CHARGE ONLY”.
False reading due to undersized or Use sufficient size DC cable sufficiently connected to
insufficiently connected DCcabling. Inverter/Charger.
Red “LOAD”Operation Inverter is overloaded.Unit will automatically shut down Reduce load. Reset by moving Operating Mode Switch to “OFF”.
Indicator Light flashing after 5 seconds. Wait 1 minute.Switch to “AUTO/REMOTE”or “CHARGE ONLY”.
* User-supplied.
OFF
(LESSER
LOAD
ON)
MAX
(GREATER
LOAD
ON)

Battery Indicator Lights

Operating Mode Switch

Operation Indicator Lights

200510095 93-2144