Tripp Lite APSINT3636VR specifications Specifications, System Overview, Output

Models: APSINT3636VR

1 4
Download 4 pages 54.4 Kb
Page 2
Image 2
Specifications

charger

OVERVIEW Supports 230V AC output from a 230V AC line power source or 36V DC battery source

SYSTEM OVERVIEW 20 millisecond automatic transfer between line and battery power supports UPS protection during blackouts and severe voltage fluctuations for equipment compatible with a one cycle transfer time

OUTPUT 3600 watts continuous AC output in inverter mode

Manual background Double Boost inverter output supports momentary startup loads up to 200% of the continuous rating for up to 10 seconds (see specification chart)

Manual background OverPower inverter output supports longer duration overloads to 150% for 1-60 minutes under ideal battery and temperature conditions. (For best results, utilize OverPower usage for as short of a duration as possible, ensure battery bank and cabling is able to provide full nominal DC voltage under load and allow inverter/charger to fully cool before and after OverPower usage.)

Manual background 3 stage, 30 amp battery charger with adjustable settings for wet/gel battery types offers fast, reliable battery recharging

Manual background Protected hardwire bolt-down input lugs safely accept heavy gauge input wiring from attached battery bank

Manual background Protected hardwire output passes 120V line power or inverter output through to connected equipment

Manual background Reliability enhanced large-transformer design with secure mounting flanges and protected DC wiring terminals

Manual background Moisture-resistant construction enables vehicular or marine operation in high humidity environments

Manual background 3 position operating mode switch supports "AUTO" mode to enable automatic transfer between DC and AC modes, CHARGE-ONLY to maintain a full battery charge when AC is present without auto transfer and SYSTEM OFF settings

Manual background Set of six front panel LEDs display AC/DC operational modes, overload status, DC voltage level, shutdown status and system fault status Manual background Set of 4 configuration dipswitches support wet/gel battery charging profiles, adjustable 259/264V high voltage auto transfer during overvoltages and selectable 144/163/182/201V AC low voltage auto transfer during brownouts

Manual background Set of 4 additional configuration dipswitches support 4 levels of charger limiting relative to output load size, a battery equalization program and battery charger low/high settings

Manual background Resettable 12A charger AC input breaker and resettable 20A AC output breaker and automatic 2 speed cooling fan protect the inverter from load and temperature related failures

Manual background Grounding lug properly connects the inverter/charger system to earth ground or vehicle grounding system

Manual background Automatic overload and thermal shutoff safely turns off inverter as excessive loads or overheating conditions develop

Manual background Front panel remote control connector enables remote off/on switching (APSRM4 remote control switch with status LED display and 50 ft cable included). APSRM4 accessory also includes user configurable jacks to support inverter shutoff or startup as a vehicle ignition is engaged

Manual background Load sensing control dial enables adjustable load threshold required to automatically turn the inverter on and off in DC mode as load conditions change

Specifications

OVERVIEW

Intended

Emergency Home Power

Application

 

 

 

SYSTEM OVERVIEW

 

Voltage

36VDC / 230VAC

compatibility

 

 

 

Frequency

50 Hz

compatibility

 

 

 

OUTPUT

 

Output watts

INVERTER MODE - 3600 watts continuous, Double Boost rated to 7200 watts peak (up to 10 seconds). Overpower

 

rating supports longer term overloads to 5400 watts for up to 15 seconds prior to inverter shutoff.

 

 

Output nominal

230V

voltage

 

 

 

Output voltage

LINE POWER (AC): Maintains 230V nominal sine wave output from line power source. INVERTER POWER (AC):

regulation

Maintains PWM sine wave output voltage of 230 VAC (+/-5%).

 

 

Output frequency

50 Hz (+/- 0.3 Hz)

regulation

 

 

 

Outlet quantity /

Hardwire

type

 

 

 

Overload

Includes 12A input breaker dedicated to the charging system and 20A output breaker for AC output loads.

protection

 

 

 

Continuous output

3600

capacity (watts)

 

 

 