Tripp Lite APSINT Series owner manual Set Configuration DIP Switches, Group A DIP Switches

Models: APSINT Series

1 12
Download 12 pages 56.86 Kb
Page 5
Image 5
Configuration

Configuration

Set Configuration DIP Switches

Using a small tool, set the Configuration DIP Switches (located on the front panel of your unit, see diagram) to optimize Inverter/Charger operation depending on your application.

B4

B3

B2

B1

 

 

 

INPUT C/B

Group B Dip Switches

 

A4

A3

A2

A1

 

OUTPUT C/B 12A

 

Group A Dip Switches

Group A DIP Switches

A1 Select Battery Type—All Models (REQUIRED)

CAUTION: The Battery Type DIP Switch setting must match the type of batteries you connect, or your batteries may be degraded or damaged over an extended period of time. See “Battery Selection,” for more information.

A4 A3 A2 A1

Battery Type

Switch Position

Gel Cell (Sealed) Battery

Up

Wet Cell (Vented) Battery

Down (factory setting)

A2 Select High AC Input Voltage Point Set Configuration DIP SwitchesGroup A DIP SwitchesGroup B DIP SwitchesManual background for Switching to Battery—APSINT2424, APSINT3636 only* (OPTIONAL)

Voltage

Switch Position

278V

Up

259V

Down (factory setting)

.

 

A2 Charger Inhibit—APSX750, APSX1250,

APSINT2012 only (OPTIONAL)

Charger

Switch Position

Inhibit

Up

Enable

Down (factory setting)

A4 A3 Select Low AC Input Voltage Point for Switching to

Battery—All Models* (OPTIONAL)

Voltage

Switch Position

201V

#A4 Up & #A3 Up

182V

#A4 Up & #A3 Down

163V

#A4 Down & #A3 Up

144V

#A4 Down & #A3 Down

 

(factory setting)

*Most of your connected appliances and equipment will perform adequately when your Inverter/Charger’s High AC Input Voltage Point is left in the factory setting and its Low AC Voltage Input Point is set to 182V. However, if the unit frequently switches to battery power due to momentary high/low line voltage swings that would have little effect on equipment operation, you may wish to adjust these settings. By increasing the High AC Voltage Point and/or decreasing the Low AC Voltage Point, you will reduce the number of times your unit switches to battery due to voltage swings.

Group B DIP Switches

B1 B2 Select Load Sharing—OPTIONAL

Your Inverter/Charger features a high-output battery charger that can draw a significant amount of AC power from your utility source or generator when charging at its maximum rate. If your unit is supplying its full AC power rating to its connected heavy electrical loads at the same time as this high charging occurs, the AC input circuit breaker could trip, resulting in the complete shut off of pass-through utility power.

To reduce the chance of tripping this breaker, Inverter/Chargers may be set to automatically limit the charger output. This keeps the sum of the unit’s AC load and charge power within the circuit breaker rating. This charger-limiting function has four settings, allowing you to reduce the charger’s draw lower and lower, as needed, if the AC input circuit breaker keeps tripping under the normal AC loads of devices you have connected downline from the unit. The figures on the next page show how to set your DIP Switches to determine how heavy the connected load can be on your Inverter/Charger before charger-limiting begins.