6– Diagrams (continued)

6-4 Battery and Breaker Diagrams (+/- 240 VDC)

Shelf 4 (Top)

 

Battery

 

Positive

Shelf 3

 

To UPS

 

Positive

 

To UPS

 

Negative

Battery

UL-Listed Breaker

Negative

To UPS

From Battery

Center Tap

Center Tap

Shelf 2

 

Shelf 1 (Bottom)

 

To Fuse or Breaker

To Center Tap

Termination

Termination

Notes:

All internal wiring is UL-listed, MTW, 125C Hi-Flex cable.

Terminal block is UL-recognized and rated for 600 VDC.

Breaker is UL-listed and rated for 250 A, 600 VDC, 25 KAIC.

Cabinets with breakers are shipped with the breaker in the off/open position.

Battery arrangements shown are typical but may vary depending on cabinet and battery type.

[13]

Page 13
Image 13
Tripp Lite Extended-Run 3-Phase Battery Cabinet owner manual Battery and Breaker Diagrams +/- 240 VDC