With power present, a battery system failure will not cause a system interruption. As long as utility power remains present, the UPS System will continue to power the connected IP telephony system without interruption and will continue to condition the power against most power anomalies. In the event of a power outage, the system will crash.

In the event of a battery system failure, the internal batteries of the UPS System and/or the external battery packs can be replaced without a service interruption.

On-Line UPS System with Internal Bypass and External Maintenance Bypass

With power present, an internal power electronics fault will result in the load automatically being powered by a bypass path inside the UPS. As long as utility power remains present, the UPS will continue to power the connected VoIP system without interruption and will continue to condition the power against basic power anomalies. In the event of a power outage, the system will crash.

In the event of a bypass condition, the power electronics module of the UPS should be replaced. This can be performed while the system remains in service, as the input and output power connections are physically and electrically separated from the power module itself. This functionality is available presently in Tripp Lite's 5-16KVA SmartOnline™ Hot-Swappable Modular UPS Systems.

With power present, a battery system failure will not cause a system interruption. As long as utility power remains present, the UPS System will continue to power the connected IP telephony system without interruption and will continue to condition the power against most power anomalies. In the event of a power outage, the system will crash.

In the event of a battery system failure, the internal batteries of the UPS System and/or the external battery packs can be replaced without a service interruption.

Line-Interactive UPS System

With power present, an internal power electronics fault can result in the load crashing. As the operational requirements of a line-interactive UPS System are very simple when power is present, this is extremely rare. Line-interactive power electronics failures are normally only detected when the power fails and the UPS attempts to power the load from its battery-driven inverter.