Tripp Lite IBRM 12/15A-L20P owner manual Specifications, Ibar, IBAR 12 ULTRA, IBAR 12/20 ULTRA

Models: IBRAM 8/20A-L20P IBRM 8/20A-L20P IBAM 12/15A-L20P IBAR 1212/20 Ultra IBRM 12/15A-L20P IBAR12/20 ULTRA IBAR 12/20 Ultra

1 4
Download 4 pages 20.8 Kb
Page 2
Image 2
Protection Present (Green LED)

DIAGNOSTIC INDICATOR LIGHTS (IBAR 12 ULTRA, IBAR 12/20 ULTRA & IBRM 8/20A-L20P)

There are three LEDs on the front panel that indicate various operating parameters when the unit is plugged into a live 120VAC/60 Hz outlet as follows, from left to right across the front of the unit:

Protection Present (Green LED)

Indicates the surge-suppression components are intact and providing full protection against spikes and surges. This LED should be lit anytime the IBAR “ON/OFF” switch is turned ON and power is present, as indicated by the lighted power switch. If the Protection Present LED does not light, then some of the surge-suppression components are not functioning and the unit should be returned for repair as soon as possible. You may still use the unit; however, connected equipment will be protected from spikes and surges at a lesser level than normal.

Line Fault (Red LED)

Indicates a wiring fault has been detected. If this LED illuminates at any time the unit is plugged in, the fault should be repaired by a qualified electrician as soon as possible. This LED indicates that phases are reversed, ground is missing or some other sort of wiring error exists in the circuit the IBAR is plugged into. The Line Fault detector circuitry will identify most common wiring faults, but will not necessarily detect every possible type of fault.

NOTE!

If the Line Fault indicator light illuminates, carefully check the AC receptacle the IBAR is plugged into. The receptacle must be tight and securely grounded. A loose AC receptacle may cause the Line Fault LED to illuminate. It must be understood that this Red LED indicates the presence of a wiring fault, but does not indicate the exact nature of the fault. Therefore, a qualified electrician should make necessary repairs.

NOTE!

If the Line Fault indicator light illuminates and power is not present at the outlets, the IBAR’s surge- suppression components have been compromised as a result of surge damage. For service, call Tripp Lite Customer Support at (773) 869-1234. Fully explain the perceived problem to the customer support person. They will either remedy the problem over the phone or give you instructions about return, repair or exchange.

Line “OK” (Green LED)

Indicates 120V AC power is present with no wiring faults detected. When this LED is illuminated, AC power is safe for connected equipment.

SPECIFICATIONS

IBAR 12

IBAR 12 ULTRA

IBAR 12/20 ULTRA

AC Energy Absorption (joules):

750

1200

1200

Surge Suppression (amp spikes)*:

60,000

96,000

96,000

UL 1449 Let-Through Rating:

400V

330V

330V

HF Noise Suppression (@ 1 MHz)

 

 

 

Filter Bank #1:

40 dB

40 dB

80 dB

Filter Bank #2:

80 dB

80 dB

-

AC Receptacles:

2 NEMA 5-15R (front)

2 NEMA 5-15R (front)

2 NEMA 5-15R (front)

 

10 NEMA 5-15R (back)

10 NEMA 5-15R (back)

6 NEMA 5-20R (back)

AC Line Cord:

12’, w/NEMA 5-15P plug

12’, w/NEMA 5-15P plug

12’, w/NEMA 5-15P plug

Circuit Breaker (Resettable):

15 amp

15 amp

20 amp

Dimensions (HxWxD, inches):

1-3/4 x 17-1/2 x 4

1-3/4 x 17-1/2 x 4

1-3/4 x 17-1/2 x 4

Weight (lbs.):

4-1/2

3

5

 

 

 

 

SPECIFICATIONS

IBRM 12/15A-L20P

IBRM 8/20A-L20P

AC Energy Absorption (joules):

1200

1200

Surge Suppression (amp spikes)*:

96,000

96,000

UL 1449 Let-Through Rating:

330V

330V

HF Noise Suppression (@ 1 MHz)

 

 

Filter Bank #1:

40 dB

80 dB

Filter Bank #2:

80 dB

-

AC Receptacles:

2 NEMA 5-15R (front)

2 NEMA 5-15R (front)

 

10 NEMA 5-15R (back)

6 NEMA 5-20R (back)

AC Line Cord:

12’, w/NEMA 5-L20P locking plug

12’, w/NEMA 5-L20P locking plug

Circuit Breaker (Resettable):

15 amp

20 amp

Dimensions (HxWxD, inches):

1-3/4 x 17-1/2 x 4

1-3/4 x 17-1/2 x 4

Weight (lbs.):

4-1/2

5

 

 

 

All Models: Nominal Input Voltage: 120VAC; Input Frequency: 50/60 Hz;

Transient Response Time: Instantaneous (0 ns).**

*Spike protection is provided in all three modes; hot to neutral, hot to ground and neutral to ground.

**Transient amplitude reduction occurs faster than the clamp response of the varistors because of the high rejection rate of the ISOBAR filter networks.

9907030 Isobar Rackmount OM DRAFT.p65 2

7/11/00, 2:22 PM

Page 2
Image 2
Tripp Lite IBRM 12/15A-L20P Specifications, Ibar, IBAR 12 ULTRA, IBAR 12/20 ULTRA, IBRM 8/20A-L20P, Line Fault Red LED