DIAGNOSTIC INDICATOR LIGHTS (IBAR 12 ULTRA, IBAR 12/20 ULTRA & IBRM
There are three LEDs on the front panel that indicate various operating parameters when the unit is plugged into a live 120VAC/60 Hz outlet as follows, from left to right across the front of the unit:
Protection Present (Green LED)
Indicates the
Line Fault (Red LED)
Indicates a wiring fault has been detected. If this LED illuminates at any time the unit is plugged in, the fault should be repaired by a qualified electrician as soon as possible. This LED indicates that phases are reversed, ground is missing or some other sort of wiring error exists in the circuit the IBAR is plugged into. The Line Fault detector circuitry will identify most common wiring faults, but will not necessarily detect every possible type of fault.
NOTE!
If the Line Fault indicator light illuminates, carefully check the AC receptacle the IBAR is plugged into. The receptacle must be tight and securely grounded. A loose AC receptacle may cause the Line Fault LED to illuminate. It must be understood that this Red LED indicates the presence of a wiring fault, but does not indicate the exact nature of the fault. Therefore, a qualified electrician should make necessary repairs.
NOTE!
If the Line Fault indicator light illuminates and power is not present at the outlets, the IBAR’s surge- suppression components have been compromised as a result of surge damage. For service, call Tripp Lite Customer Support at (773)
Line “OK” (Green LED)
Indicates 120V AC power is present with no wiring faults detected. When this LED is illuminated, AC power is safe for connected equipment.
SPECIFICATIONS | IBAR 12 | IBAR 12 ULTRA | IBAR 12/20 ULTRA |
AC Energy Absorption (joules): | 750 | 1200 | 1200 |
Surge Suppression (amp spikes)*: | 60,000 | 96,000 | 96,000 |
UL 1449 | 400V | 330V | 330V |
HF Noise Suppression (@ 1 MHz) |
|
|
|
Filter Bank #1: | 40 dB | 40 dB | 80 dB |
Filter Bank #2: | 80 dB | 80 dB | - |
AC Receptacles: | 2 NEMA | 2 NEMA | 2 NEMA |
| 10 NEMA | 10 NEMA | 6 NEMA |
AC Line Cord: | 12’, w/NEMA | 12’, w/NEMA | 12’, w/NEMA |
Circuit Breaker (Resettable): | 15 amp | 15 amp | 20 amp |
Dimensions (HxWxD, inches): | |||
Weight (lbs.): | 3 | 5 | |
|
|
|
|
SPECIFICATIONS | IBRM | IBRM |
AC Energy Absorption (joules): | 1200 | 1200 |
Surge Suppression (amp spikes)*: | 96,000 | 96,000 |
UL 1449 | 330V | 330V |
HF Noise Suppression (@ 1 MHz) |
|
|
Filter Bank #1: | 40 dB | 80 dB |
Filter Bank #2: | 80 dB | - |
AC Receptacles: | 2 NEMA | 2 NEMA |
| 10 NEMA | 6 NEMA |
AC Line Cord: | 12’, w/NEMA | 12’, w/NEMA |
Circuit Breaker (Resettable): | 15 amp | 20 amp |
Dimensions (HxWxD, inches): | ||
Weight (lbs.): | 5 | |
|
|
|
All Models: Nominal Input Voltage: 120VAC; Input Frequency: 50/60 Hz;
Transient Response Time: Instantaneous (0 ns).**
*Spike protection is provided in all three modes; hot to neutral, hot to ground and neutral to ground.
**Transient amplitude reduction occurs faster than the clamp response of the varistors because of the high rejection rate of the ISOBAR filter networks.
9907030 Isobar Rackmount OM DRAFT.p65 2 | 7/11/00, 2:22 PM |