Storage & Service

Storage

First turn your UPS OFF and disconnect its power cord from the wall outlet. Then disconnect all equipment to avoid battery drain. If you plan on storing your UPS for an extended period of time, fully recharge the UPS batteries once every three months by plugging the UPS into a live AC outlet and letting the UPS charge for 4 to 6 hours. If you leave your UPS batteries discharged for an extended period of time, they will suffer a permanent loss of capacity.

Service

If returning your UPS for service, contact your local Tripp Lite dealer or distributor. They will refer you to a service center. Please carefully pack the UPS using the ORIGINAL PACKING MATERIAL that came with the unit. Enclose a letter describing the symptoms of the problem. If the UPS is within the warranty period, enclose a copy of your sales receipt.

Specifications

OmniSmart INT 300 PNP

OmniSmart INT 500 PNP

OmniSmart INT 700 PNP

Output Capacity (VA/Watts):

300/180

500/280

700/425

Battery Runtime (Half Load/

 

 

 

Full Load) Minutes:

17/5

17/5

17/5

Typical Runtime (Desktop

 

 

 

PC/15 in. monitor) Minutes:

30

30

45

Battery Recharge Time:

2-4 hrs.

2-4 hrs.

2-4 hrs.

Approvals:

UL, cUL, CE

UL, cUL, CE

UL, cUL, CE

Modem/Fax Protection

 

 

 

(starts at 260V):

1 line

1 line

2 line

OmniSmart INT 1000 PNP

OmniSmart INT 1400 PNP

Output Capacity (VA/Watts):

1000/680

1400/940

Battery Runtime (Half Load/

 

 

Full Load) Minutes:

23/7

24/8

Typical Runtime (Desktop

 

 

PC/15 in. monitor) Minutes:

55

75

Battery Recharge Time:

2-4 hrs.

2-4 hrs..

Approvals:

UL, cUL, CE

UL, cUL, CE

Modem/Fax Protection

 

 

(starts at 260V):

 

OmniPro INT 280

OmniPro INT 450 PNP

Output Capacity (VA/Watts):

280/175

450/280

Battery Runtime (Half Load/

 

 

Full Load) Minutes:

17/5

17/5

Typical Runtime (Desktop

 

 

PC/15 in. monitor) Minutes:

15

30

Battery Recharge Time:

2-4 hrs.

2-4- hrs.

Approvals:

UL, cUL, CE

UL, cUL, CE

Modem/Fax Protection

 

 

(starts at 260V):

ALL MODELS:

Input Voltage, Frequency (230V, 50/60 Hz); On-Line Input Voltage Range (144 - 282 volts); Voltage-Regulated Output Voltage Range (230V +6% / -12%); On Battery Output Voltage Range (230V +/- 5%); Output Waveform Line Mode (filtered sinewave); Output Waveform Battery Mode (PWM sine wave); AC Surge Suppression (exceeds IEEE 587 Cat. A & B standards); AC Noise Attenuation (>40 dB); AC Protection Modes (H to N, H to G, N to G).