1.Introduction
1.1Product Features
The RELAYIOCARD is a programmable UPS management device featuring:
•6 programmable relay output contacts
•Configurable normal open or normal close for each relay contact
•Configurable UPS shutdown delay time
•Configurable input signal to shutdown UPS or test battery
The RELAYIOCARD allows you to:
•Monitor UPS status and events
•Perform remote system shutdowns and battery tests
1.2 Package Contents
This Package Contains:
•RELAYIOCARD
•Configuration Cable
•Faceplates
•Owner’s Manual
2.Installation and Setup
2.1 System Requirements
The RELAYIOCARD supports all Tripp Lite SmartOnline™ UPS Systems and select SmartPro™ UPS Systems, including SMART1050SLT, SMART1500SLT, SMART2200RMXL2U, SMX1050SLT, SMX1500SLT, SMART3000SLT, SMART2200SLT, SM2200RMNAFTA, SMART2600RM2U, SMART3000RM2U, SMART1500CRMXL, SMART1500SLTXL, SMART750XLa, SMX3000XLRT2U and SMX2200XLRT2U. Supported systems must run a UPS protocol of 3008 or above.
To determine your UPS protocol:
1.Open Tripp Lite PowerAlert software.
2.Click on the “Misc” button on the main screen of the PowerAlert console.
3.View the protocol variable.
2.2 Communications Setup
1.Connect Tx to pin2, Rx to pin 3 and
2.In the Windows environment, launch the Hyper Terminal program, then open the specified COM port.
3.Set the following properties – Baud rate: 2400, Data Bits: 8, Parity: None, Stop Bit: 1, Flow Control: None.
2
200805102 | 7/15/2008 9:19:00 AM |