USB, serial and EPO cabling

Owner's manual with warranty information

Features

SmartPro line interactive UPS system is ideal for voice, data, medical and industrial networking applications

Line interactive Automatic Voltage Regulation (AVR) offers two levels of voltage boost during brownouts and one level of voltage cut during overvoltages

Maintaints continuous operation through blackouts, voltage fluctuations and surges

Corrects line voltage conditions as low as 83V and as high as 145 back to selectable 100/110/120V nominal values

Standard internal battery set offers 16 minutes at half load (800w) and 6 minutes at full load (1600w)

Optional BP48V24-2U and BP48V60RT3U external rack/tower battery packs enable extended runtime operation

Compact rackmount form factor installs using only 2 rack spaces (2U) with a maximum installed depth of only 19 inches

Ships with all mounting accessories for 4 post rackmount installation

Optional 2POSTRMKITWM enables 2 post rackmount or wallmount installation

Optional 2-9USTAND accessory enables small-footprint upright tower placement

Network interfaces support simultaneous communications via built-in USB, DB9 serial and SNMPWEBCARD slot

HID compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, with the built-in ability to shutdown any number of additional servers over IP

UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current, battery capacity, AC line frequency, timed inverter sutoff, activate self-test, load bank output power control and remote reboot

Built-in Emergency Power Off (EPO) interface with cable

NEMA 5-20P input plug (user-installable NEMA 5-15P replacement plug included) / NEMA 5-15R & NEMA 5-15/20R output receptacles Integrated 3 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual load banks (Each bank controls 1 outlet per load bank)

Front panel LEDs offer current monitoring and battery charge level information

UPS ships fully assembled in full compliance with DOT regulations, no time consuming connection of internal batteries by user required 2 year manufacturer's product warranty, $250,000 ULtimate Lifetime Insurance

Specifications

SYSTEM OVERVIEW

Voltage compatibility

120V factory default (110V, 100V user selectable)

 

 

Frequency

50 / 60 Hz

compatibility

 

 

 

OUTPUT

 

Output VA

2200

 

 

Output watts

1600

 

 

Output nominal

120V (110V, 100V) VAC

voltage

 

 

 

Output voltage

LINE MODE: Sine wave line voltage 120V (-18% / +8%)

regulation

 

 

 

Output frequency

LINE MODE: Passes line frequency of 60Hz +/-10%

regulation

 

 

 

Outlet quantity / type

4 NEMA 5-15R and 4 NEMA 5-15/20R

 

 

Customized load

3 single outlet load banks

management

 

receptacles

 

 

 

INPUT

 

Maximum input amps

13.3 (120V)/ 14.6 (110V)/ 16.0 (100V)

 

 

Input connection type

NEMA 5-20P (optional, user-installable NEMA 5-15P included in box)

Page 2