Specifications

SYSTEM OVERVIEW Dual boost AVR circuits boost undervoltages by 14% or 24% depending on the severity and reduces overvoltages by 12%

OUTPUT Network interfaces support simultaneous communications via 2 USB, 2 DB9 serial and SNMPWEBCARD slot

INPUT Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus any number of additional servers over IP

BATTERY Communications ports support on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current, battery capacity, internal UPS temperature, AC line frequency, timed inverter shutoff, activate self-test and load bank output power control

Manual background Built in Emergency Power Off (EPO) interface with cable

Manual background Sine wave output in AC and battery modes

Manual background Expandable runtime with optional battery packs â" BP48V24-2U (limit 1) and BP48V60RT-3U (multi-pack compatible)

Manual background Half load runtime of 11 minutes (1125 watts)

Manual background Full load runtime of 4 minutes (2250 watts)

Manual background Includes 9 output receptacles arranged in 3 load banks (4 NEMA 5-15R / 4 NEMA 5-15/20R / 1 NEMA L5-30R)

Manual background Ships with NEMA L5-30P input plug, user installable NEMA 5-20P replacement plug included

Manual background Integrated 3 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual devices

Manual background 3 stage metered LEDs offer current monitoring and battery charge level

Manual background Mains power and voltage regulation LEDs offer at-a-glance power status information

Manual background Front panel switches support self-test and alarm cancel functions

Manual background Included UPSRMRII adjustable mounting rails support installation in 19 inch racks with a front-to-rear depth of 23.5 and 36.5 inches (add a 2nd UPSRMRII accessory to extend the reach to 35.25 to 49.5 inches)

Manual background UPS ships fully assembled in full compliance with DOT regulations, no time consuming connection of internal batteries by user required

Manual background Supports 2 post rackmount and wallmount installation with optional 2POSTRMKITWM accessory

Manual background Supports upright tower placement with optional 2-9USTAND accessory

Manual background UL (USA), cUL (Canada), NOM (Mexico), FCC Class A (Emissions) listed

Manual background 2 year manufacturer's product warranty, $250,000 Ultimate Lifetime Insurance

Specifications

SYSTEM OVERVIEW

Voltage compatibility

120V AC

 

 

Frequency

60 Hz

compatibility

 

 

 

OUTPUT

 

Output VA

3000

 

 

Output watts

2250

 

 

Output nominal

120V AC

voltage

 

 

 

Output voltage

LINE MODE: Sine wave line voltage 120V (-18% / +8%)

regulation

 

 

 

Output frequency

LINE MODE: Passes line frequency of 60Hz +/-10%

regulation

 

 

 

Outlet quantity / type

4 NEMA 5-15R, 4 NEMA 5-15/20R and 1 NEMA L5-30R

 

 

Customized load

3 single outlet load banks with integraded switched PDU supports load shedding and remote reboot on demand of

management

locked network devices. Controllable via PowerAlert software to switch off optional loads, like monitors, to increase

receptacles

available runtime for servers and other critical devices.

 

 

Overload protection

Resettable circuit breaker

 

 

INPUT

 

Maximum input

24A

amps

 

 

 

Input connection

NEMA L5-30P (includes user installable NEMA 5-20P replacement plug)

type

 

 

 

Input cord length

10 ft., 10 gauge

 

 

Recommended

30A 120V

Electrical Service

 

 

 