Full load runtime
Half load runtime
Expandable battery runtime
DC system voltage
Typical battery lifespan
Battery recharge rate
Replacement Battery Cartridge
4 minutes (3000VA)
11 minutes (1500VA)
Supports extended runtime with optional external battery packs BP48V242U (limit 1) and BP48V60RT3U
48V DC
6.5hours
VOLTAGE REGULATION
Voltage regulation description
Overvoltage correction
Direct pass through
Brownout correction
Severe brownout correction
Automatic Voltage Regulation (AVR) circuits maintain clean, regulated
Input voltages between 128 and 147V AC are reduced by 12%
Input voltages between 105 and 127V AC are passed on to connected equipment unchanged
Input voltages between 95 and 104V AC are boosted by 12%
Input voltages between 79 and 94V AC are boosted by 24%
LEDS ALARMS & SWITCHES
Front panel LEDs
Alarms
Switches
5 front panel LEDs â Green POWER LED, Green VOLTAGE CORRECTION LED, 3 color BATTERY CHARGE LED, 3 color OUTPUT LOAD LED, red BATTERY WARNING LED
3 function audible alarm indicates power failure conditions (4 short beeps every 10 seconds), overload (continuous short beeps) and low battery (continuous tone)
Yes, includes 2 front panel mounted
SURGE / NOISE SUPPRESSION
AC surge | 480 joules |
suppression |
|
|
|
AC suppression | Instantaneous |
response time |
|
|
|
EMI / RFI AC noise | Yes |
suppression |
|
|
|
PHYSICAL |
|
Shipping weight (lbs) | 72 |
|
|
Shipping weight (kg) | 32.7 |
|
|
Shipping | 9 x 23.5 x 20 |
Dimensions |
|
(HWD/in) |
|
|
|
Shipping Dimensions (HWD/cm)
22.9 x 59.7 x 50.8
Unit weight (lbs)
Unit weight (kg)
Unit Dimensions (HWD/in)
Unit Dimensions (HWD/cm)
Material of construction
64
29.1
3.5x 17.5 x 19
8.89x 44.5 x 48.3
Steel