severity and reduces overvoltages by 12%

Network interfaces support simultaneous communications via USB, DB9 serial and SNMPWEBCARD slot

Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus any number of additional servers over IP

Communications ports support on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current, battery capacity, internal UPS temperature, AC line frequency, timed inverter shutoff, activate self-test and load bank output power control

Built in Emergency Power Off (EPO) interface with cable

Sine wave output in AC and battery modes

Half load runtime of 15 minutes (500VA/320 watts)/Full load runtime of 7 minutes (1000VA/640 watts)

Includes 6 NEMA 5-15R output receptacles arranged in 2 switchable single-outlet load banks

Integrated 2 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual devices

3 stage metered LEDs offer current monitoring and battery charge level

Mains power and voltage regulation LEDs offer at-a-glance power status information

Front panel switches support self-test and alarm cancel functions

UPS ships fully assembled in full compliance with DOT regulations, no time consuming connection of internal batteries by user required

UL (USA), cUL (Canada), NOM (Mexico), FCC Class A (Emissions) listed

2 year manufacturer's product warranty, $250,000 Ultimate Lifetime Insurance

Specifications

SYSTEM OVERVIEW

Voltage compatibility

120 VAC

 

 

Frequency

60 Hz

compatibility

 

 

 

OUTPUT

 

Output VA

1000

 

 

Output watts

640

 

 

Output nominal

120VAC sine wave output in AC and battery mode

voltage

 

 

 

Output voltage

LINE MODE: Sine wave line voltage 120V (-21% +8%), BATTERY MODE: Sine wave output within 5% of 120VAC

regulation

 

 

 

Output frequency

LINE MODE: Passes line frequency of 60Hz +/-10% BATTERY MODE: Inverter output regulated to 60Hz +/-0.5Hz

regulation

 

 

 

Outlet quantity / type

6 NEMA 5-15R

 

 

Customized load

"Includes 2 load banks, each with 2 outlets that support automated load shedding and remote reboot on demand of

management

locked network devices. Configurable via PowerAlert software to automatically switch off optional loads, like monitors, to

receptacles

increase available runtime for servers and other critical devices. "

 

 

Overload protection

Via 15A input breaker

 

 

INPUT

 

Maximum input

9.2A

amps

 

 

 

Input connection

NEMA 5-15P

type

 

 

 

Input cord length

10 ft., 14 gauge

 

 

Recommended

15A 120V

Electrical Service

 

 

 

BATTERY

 

Full load runtime

7 minutes (640 watts)

 

 

Half load runtime

15 minutes (320 watts)

 

 

DC system voltage

24 VDC

 

 

Typical battery

3-6 years, depending on usage

lifespan

 

 

 