Battery recharge rate
Replacement Battery Cartridge
VOLTAGE REGULATION
Voltage regulation description
Overvoltage correction
Brownout correction
Line interactive voltage regulation system corrects input voltages between 83 and 147 back to usable 120V nominal levels.
Input voltages between 128 and 147 are reduced by 12%
Input voltages between 83 and 107 are boosted by 14%
LEDS ALARMS & SWITCHES
Front panel LEDs
Alarms
Switches
5 front panel LEDs - Green POWER LED, 3 color BATTERY CHARGE LED, 3 color OUTPUT LOAD LEVEL LED, red
BATTERY WARNING LED.
3 function audible alarm indicates power failure conditions (4 short beeps every 10 seconds), overload (continuous short beeps) and low battery (continuous tone)
Yes, includes 2 front panel mounted
SURGE / NOISE SUPPRESSION
AC surge | 480 joules |
suppression |
|
|
|
AC suppression | Instantaneous |
response time |
|
|
|
EMI / RFI AC noise | Yes |
suppression |
|
|
|
PHYSICAL |
|
Shipping weight | 36 |
(lbs) |
|
|
|
Shipping weight (kg) | 16.3 |
|
|
Shipping | 6.25 x 23.5 x 22.5 |
Dimensions |
|
(HWD/in) |
|
|
|
Shipping Dimensions (HWD/cm)
15.9 x 60 x 57.2
Unit weight (lbs) | 32 |
|
|
Unit weight (kg) | 14.5 |
|
|
Unit Dimensions | 1.75 x 17.5 x 16.75 |
(HWD/in) |
|
|
|
Unit Dimensions | 44.5 x 44.5 x 42.5 |
(HWD/cm) |
|
|
|
Material of | Steel |
construction |
|
|
|
Form factors | Rack (1U) |
supported |
|
|
|
Cooling method | |
|
|
Battery Access | Battery access door allows hot swap battery replacement without powering connected equipment off |
|
|
ENVIRONMENTAL |
|
Relative Humidity 0 to 95%,
Storage Temperature +5 to +122 degrees Fahrenheit /
Operating+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Temperature
Line mode BTU/hr. | 55.8 |
(Max.) |
|
|
|