Relative Humidity
Storage
Temperature
0 to 95%,
+5 to +122 degrees Fahrenheit
Operating | +32 to +104 degrees Fahrenheit |
Temperature |
|
|
|
COMMUNICATIONS |
|
Network | Includes 2 |
monitoring port | voltage, DC battery voltage, load percentage, battery charge current, battery capacity, internal UPS temperature, line |
| frequency status messaging. Interface supports timed inverter shutoff after unattended shutdown, activate |
| second reboot of connected equipment. Supports individual reboot of selected items connected to load management |
| receptacles and load shedding to increase battery runtime for the most critical loads. Compatible with Tripp Lite's |
| PowerAlert and Watchdog service software. |
|
|
Software and cabling included
SNMP compatibility
WatchDog compatibility
Includes PowerAlert UPS monitoring software for all common network and standalone operating systems. Ships with 2 cables,
Yes via external SNMP adapter accessory #SNMPWEBSOLO
Yes, compatible with Tripp Lite's Watchdog system service to restore operation to locked equipment through soft reboot of application / OS or hard power off/on reboot of connected equipment - ideal for unattended kiosk applications
LINE / BATTERY TRANSFER
Transfer time from line power to battery mode
Low voltage transfer to battery power
High voltage transfer to battery power
Switches to battery power as line voltage decreases to 75 volts or less. Resets back to line power mode as line voltage increases to 79V or higher.
Switches to battery power as line voltage increases to 147 volts or higher. Resets back to line power mode as line voltage decreases to 143V or less.
SPECIAL FEATURES
Cold Start | Yes, inverter can be "cold started" to enable temporary AC output during a power failure |
|
|
Appearance | Attractive gray tower UPS |
|
|
CERTIFICATIONS |
|
Certifications | Tested to UL1778 (USA), cUL (Canada), Class A (emissions), NOM (Mexico) |
|
|
WARRANTY |
|
Product Warranty | 2 year product warranty |
Period |
|
|
|
Connected | $250,000 connected equipment insurance (USA / Canada only) |
Equipment |
|
Coverage |
|
|
|
Optional Coverage