DC system voltage
Typical battery lifespan
Battery recharge rate
Replacement Battery Cartridge
36 V DC
RBC53
VOLTAGE REGULATION
Voltage regulation description
Overvoltage correction
Direct pass through
Brownout correction
Severe brownout correction
Automatic Voltage Regulation (AVR) circuits maintain clean, regulated
Input voltages between 128 and 147V AC are reduced by 12%
Input voltages between 108 and 127V AC are passed on to connected equipment unchanged
Input voltages between 93 and 107V AC are boosted by 14%
Input voltages between 75 and 92V AC are boosted by 30%
LEDS ALARMS & SWITCHES
Front panel LEDs
Alarms
Switches
Includes 5 front panel LEDs to indicate BATTERY CHARGE LEVEL, AC LINE POWER STATUS, VOLTAGE REGULATION STATUS, UPS LOAD LEVEL and BATTERY LOW / REPLACE information
Audible alarm indicates power failure conditions (4 short beeps every 10 seconds), overload (continuous short beeps) and low battery (continuous tone)
Yes, includes 2 front panel mounted
SURGE / NOISE SUPPRESSION
AC surge | 480 joules |
suppression |
|
|
|
AC suppression | Instantaneous |
response time |
|
|
|
EMI / RFI AC | Yes |
noise |
|
suppression |
|
|
|
PHYSICAL |
|
Shipping weight | 42.6 |
(lbs) |
|
|
|
Shipping weight | 19.4 |
(kg) |
|
|
|
Unit weight (lbs) | 38.4 |
|
|
Unit weight (kg) | 17.5 |
|
|
Unit Dimensions | 12.75 x 7.5 x 9 |
(HWD/in) |
|
|
|
Unit Dimensions | 32.4 x 19.1 x 22.9 |
(HWD/cm) |
|
|
|
Material of | PVC |
construction |
|
|
|
Form factors | Tower |
supported |
|
|
|
Cooling method | |
|
|
Battery Access | Battery access door allows hot swap battery replacement without powering connected equipment off |
|
|